Introduction Diagram 17.1 Components of a firefighting shaft

Diagram 17.1 Components of a firefighting shaft

Diagram 17.1 Components of a firefighting shaft. Wording on the drawing: See para 17.1; Any building; Fire main outlet; Firefighting stairs; Firefighting; lobby; Firefighting; lift in lift shaft; Minimum fire resistance REI 120 from accommodation side and REI 60 from inside the shaft with E 60 Sa fire doors; Minimum fire resistance REI 60 from both sides with E 30 Sa fire doors; NOTES:; 1. Outlets from a fire main should be located in the firefighting lobby.; 3. This diagram is only to illustrate the basic components and is not meant to represent the only acceptable layout. The firefighting shaft should be constructed generally in accordance with Section 6 of BS 9999.; 2. A firefighting lift is required if the building has a floor more than 18m above, or more than 10m below, fire service vehicle access level.; 4. For the minimum fire resistance of lift doors see Table C1.