Section 17: Access to buildings for firefighting personnel Introduction

Introduction

17.1

Facilities for fire and rescue, such as firefighting lifts, firefighting stairs and firefighting lobbies, are combined in protected firefighting shafts (Diagram 17.1). Section 8 gives guidance on the design and construction of protected shafts.

Diagram 17.1 Components of a firefighting shaft

Diagram 17.1 Components of a firefighting shaft. Wording on the drawing: See para 17.1; Any building; Fire main outlet; Firefighting stairs; Firefighting; lobby; Firefighting; lift in lift shaft; Minimum fire resistance REI 120 from accommodation side and REI 60 from inside the shaft with E 60 Sa fire doors; Minimum fire resistance REI 60 from both sides with E 30 Sa fire doors; NOTES:; 1. Outlets from a fire main should be located in the firefighting lobby.; 3. This diagram is only to illustrate the basic components and is not meant to represent the only acceptable layout. The firefighting shaft should be constructed generally in accordance with Section 6 of BS 9999.; 2. A firefighting lift is required if the building has a floor more than 18m above, or more than 10m below, fire service vehicle access level.; 4. For the minimum fire resistance of lift doors see Table C1.
Diagram 17.1 Components of a firefighting shaft