Provision of firefighting shafts Diagram 17.2 Provision of firefighting shafts

Diagram 17.2 Provision of firefighting shafts

Diagram 17.2 Provision of firefighting shafts. Wording on the drawing: See para 17.2; Buildings in which firefighting shafts should be provided,; showing which storeys need to be served; a. Any building b. Any building c. ‘Shop and d. Any building commercial’, The upper storeys The basement The basement ‘assembly and in any building storeys in any storeys in any recreation’ and with a storey more building with a building with two ‘industrial’ than 18m above basement more or more buildings (purpose fire service vehicle than 10m below basements each groups 4, 5 and 6) access level fire service vehicle exceeding 900m² access level; The upper storeys in purpose groups 4, 5 and 6 buildings with a storey of 900m2 or more which is more than 7.5m above fire service vehicle access level; > 18m; Fire service vehicle; > 7.5m; access; level; > 10m; Two or more basement storeys each exceeding 900m²; NOTES:; 1. Height excludes any top storey(s) consisting exclusively of plant rooms.; Extent of firefighting; Extent of firefighting; stair lift 2. Firefighting shafts should serve all floors through which they pass.
Diagram 17.2 Provision of firefighting shafts