Width of escape stairs Discounting of stairs
Discounting of stairs
3.14
Regardless of escape strategy, where two or more stairs are provided, it should be assumed that one might not be available during a fire. Each stair should be discounted in turn to ensure the capacity of the remaining stairs is adequate. This applies to buildings with or without a sprinkler system.
3.15
Paragraph 3.14 does not apply if either of the following applies.
a. Escape stairs are protected by a smoke control system designed in accordance with BS EN 12101-6.
b. Escape stairs are approached on each storey (except the top storey) through a protected lobby.
Despite these exceptions, at least one storey exit still needs to be discounted (paragraph 2.21).
Paragraph 3.34 identifies cases where stairs need lobby protection.