Section 3: Design for vertical escape Width of escape stairs

Width of escape stairs

3.10

The width of escape stairs should meet all of the following conditions.

a. It should be at least as wide as any exits giving access to the stairs.
b. It should be no less than the minimum widths given in Table 3.1.
c. It should not reduce at any point on the way to a final exit.
d. It should not exceed 1400mm in stairs taller than 30m, unless a central handrail is provided. When a central handrail is provided, the stair width on each side of it should be considered separately when assessing stair capacity.

3.11

Approved Document K requires stairs more than 2000mm wide in public buildings to have a central handrail.

3.12

If an exit route from a stair is also the escape route from the ground storey and/or basement storey, the width of the exit route may need to be increased (see paragraph 2.23).

Table 3.1 Minimum widths of escape stairs

Situation of stairMaximum number of people served(1) Minimum stair width (mm)
1a. In a ‘residential (institutional)’ building (unless the stair will only be used by staff)
1501000(2)
1b. In an ‘assembly and recreation’ building and serving an area used for assembly purposes (unless the area is less than 100m²)
2201100
1c. In any other building and serving an area with an occupancy of more than 50
Over 220See note 3
2. Any stair not described above
50800(4)

NOTES:

1. Assessed as likely to use the stair in a fire emergency.
2. Section 6 of BS 9999 recommends that firefighting stairs should be at least 1100mm wide.
3. See Table 3.2 for the size of stairs for simultaneous evacuation, and Table 3.3 for phased evacuation.
4. To comply with the guidance in Approved Document M on minimum widths for areas accessible to disabled people, this may need to be increased to 1000mm.

Calculation of minimum stair width

3.13

The width depends on the number of stairs provided and the escape strategy (simultaneous or phased evacuation). If the maximum number of people needing to use escape stairs is unknown, calculate it using the floor space factors in Appendix D.

Discounting of stairs

3.14

Regardless of escape strategy, where two or more stairs are provided, it should be assumed that one might not be available during a fire. Each stair should be discounted in turn to ensure the capacity of the remaining stairs is adequate. This applies to buildings with or without a sprinkler system.

3.15

Paragraph 3.14 does not apply if either of the following applies.

a. Escape stairs are protected by a smoke control system designed in accordance with BS EN 12101-6.
b. Escape stairs are approached on each storey (except the top storey) through a protected lobby.

Despite these exceptions, at least one storey exit still needs to be discounted (paragraph 2.21).

Paragraph 3.34 identifies cases where stairs need lobby protection.

Simultaneous evacuation

3.16

The width of escape stairs should take account of the number of people using them while evacuating all storeys at the same time. The following stairs should be designed to allow simultaneous evacuation.

a. All stairs serving basements.
b. All stairs serving buildings with open spatial planning.
c. All stairs serving ‘residential (other)’ (purpose group 2(b)) or ‘assembly and recreation’ (purpose group 5) buildings.

Annexes B and C of BS 9999 include designs based on simultaneous evacuation.

3.17

The capacity of stairs of widths from 1000mm to 1800mm is given in Table 3.2.

Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building

No. of floors servedMaximum number of people served by a stair of width:
1000mm1100mm1200mm1300mm1400mm1500mm1600mm1700mm1800mm
1150220240260280300320340360
2190260285310335360385410435
3230300330360390420450480510
4270340375410445480515550585
5310380420460500540580620660
6350420465510555600645690735
7390460510560610660710760810
8430500555610665720775830885
9470540600660720780840900960
105105806457107758409059701035

NOTES:

1. The capacity of stairs that serve more than 10 storeys may be obtained by using linear extrapolation.
2. The capacity of stairs not less than 1100mm wide may also be obtained by using the formulas in paragraph 3.18.
3. Unless a central handrail is provided, stairs with a rise of more than 30m should be a maximum width of 1400mm (see paragraph 3.10).
4. Stairs wider than 2000mm should have a central handrail (see paragraph 3.11).

3.18

As an alternative to Table 3.2, the capacity of stairs 1100mm wide or wider can be found using either of the following formulas:

a. P = 200W + 50 (W – 0.3)(N – 1)
b. W = P + 15N – 15 / 150 + 50N

where:

P is the number of people that can be served

W is the width of the stair, in metres

N is the number of storeys served.

Separate calculations should be made for stairs serving basement storeys and stairs serving upper storeys.

The population, P, should be divided by the number of available stairs.

The formula is useful to determine the width of stairs where people are not distributed evenly – either within a storey or between storeys.

In the formula, 200W represents the number of people estimated to have left the stair after 2.5 minutes of evacuation, and 50 (W – 0.3)(N – 1) represents the number of people estimated to be on the stair after 2.5 minutes of evacuation.

Worked examples

A 14 storey building contains 12 storeys of offices (ground + 11). The top two storeys contain flats that are served by separate stairs. What is the minimum width needed for the stairs that serve the office floors, for simultaneous evacuation? In the 11 above-ground-floor offices, 1200 people use the stairs. (People in the ground floor offices do not use the stairs.) In this example, two stairs are shown to satisfy the travel distance limitations.
a. The population is distributed evenly
The top office storey is at a height greater than 18m, therefore both stairs need lobby protection (see paragraph 3.34). Because both stairs are entered at each level via a protected lobby, both stairs can be assumed to be available (see paragraph 3.15).
P = 1200/2 = 600, N = 11
From the formula:
600 = 200W + 50 (W – 0.3)(11 – 1)
600 = 200W + (50W – 15)(10)
600 = 200W + 500W – 150
750 = 700W
W = 1070mm
Therefore both stairs should be at least 1070mm wide. But this needs to be increased to 1100mm, because the formula applies to stairs 1100mm wide or wider (see paragraph 3.18).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum widths needed for 110 people in Table 2.3).
b. The population is not distributed evenly
(e.g. 1000 people occupy floors 1 to 9, and 200 occupy floors 10 and 11).
The top office storey is at a height greater than 18m, therefore both stairs need lobby protection (see paragraph 3.34). Because both stairs are entered at each level via a protected lobby, both stairs can be assumed to be available (see paragraph 3.15).
To find the width of:
• the stairs serving floors 10 and 11:
P = 200/2 = 100, N = 2
From the formula:
100 = 200W + 50 (W – 0.3)(2 – 1)
100 = 200W + (50W – 15)(1)
100 = 200W + 50W – 15
115 = 250W
W = 460mm
Therefore both stairs between the 9th floor landing and the top floor should be at least 460mm wide. But this needs to be increased to 1100mm, because the formula applies to stairs 1100mm wide or wider (see paragraph 3.18).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum widths needed for 100 people in Table 2.3).
• the stairs serving floors 1 to 9:
P = 1200/2 = 600, N = 9
From the formula:
600 = 200W + 50 (W – 0.3)(9 – 1)
600 = 200W + (50W – 15)(8)
600 = 200W + 400W – 120
720 = 600W
W = 1200mm
Therefore both stairs between the ninth floor landing and the ground floor should be at least 1200mm wide.
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum widths needed for 134 people in Table 2.3).

Phased evacuation

3.19

Phased evacuation cannot be used in every type of building, but can be advantageous for escape stairs in high buildings. It requires supporting facilities, such as fire detection and alarm systems, to be provided and maintained.

In a phased evacuation, the first people to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, subsequent evacuation is done two floors at a time, reducing disruption in large buildings.

Phased evacuation enables stairs to be narrower than with simultaneous evacuation, and may be used for any building provided it is not identified in paragraph 3.16.

3.20

Phased evacuation in buildings with a storey over 30m in height introduces the potential for escaping people to impede firefighters entering and operating within the building. This can be addressed by consulting with the fire and rescue service about special management procedures.

In very tall buildings, typically with a storey over 45m in height, physical measures may need to be incorporated, such as by discounting a stair.

3.21

A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.

a. At each storey except a top storey, stairs should be approached through a protected lobby or protected corridor.
b. At each storey, the lifts should be approached through a protected lobby (see paragraph 5.37).
c. Every floor should be a compartment floor (REI depending on height and use of the building).
d. If there is a storey over 30m above ground level, the building should be protected throughout by an automatic sprinkler system in accordance with Appendix E.
e. The building should be fitted with an appropriate fire warning system conforming to at least the L3 standard given in BS 5839-1.
f. An internal speech communication system should provide communication between a control point at fire and rescue service access level and a fire warden on every storey. The recommendations for phased evacuation provided in BS 5839-1 should be followed. Where it is deemed appropriate to install a voice alarm, this should be in accordance with BS 5839-8.

3.22

The minimum width of stairs needed for phased evacuation is given in Table 3.3.

Table 3.3 Minimum width of stairs designed for phased evacuation

Maximum number of people in any storeyStair width (mm)
1001000
1201100
1301200
1401300
1501400
1601500
1701600
1801700
1901800

NOTES:

1. This table assumes a phased evacuation of the fire floor first followed by evacuation of not more than two floors at a time.
2. Unless a central handrail is provided, stairs with a rise of more than 30m should be a maximum width of 1400mm (see paragraph 3.10).
3. As an alternative to using this table, the minimum width (in mm) may be calculated from: (P×10) – 100 where P = the number of people on the most heavily occupied storey. However, the minimum width of a stair should be 1000mm.

Worked example using Table 3.3

What is the minimum width needed for the stairs serving a 15 storey office building (ground + 14 office floors), assuming a total population of 2500 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, three stairs are required.

The building is over 45m in height and designed for phased evacuation. It has been decided to discount one stair to take account of fire and rescue service operations as described in paragraph 3.20. Therefore:

• Number of people per storey = 2500/14 = 179.

Each remaining stair must be able to accommodate half the population of one storey (i.e. 90 people).

Thus each stair should be 1000mm wide (maximum capacity 100 people).

This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum width needed for 90 people in Table 2.3).

• At least one of those stairs needs to be a firefighting stair, therefore a minimum width of 1100mm is needed (see note 2 to Table 3.1).

Additional worked example using Table 3.3

What is the minimum width needed for the stairs serving a 9 storey office building (ground + 8 office floors), assuming a total population of 1920 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, two stairs are required.

As both stairs need to be entered at each level through a protected lobby (see paragraph 3.21), both stairs can be assumed to be available (see paragraph 3.15). Therefore:

• Number of people per storey = 1920/8 = 240.
• Each stair must be able to accommodate half the population of one storey (i.e. 240/2 = 120 people).
• Thus both stairs would require a width of 1100mm (maximum capacity 120 people) according to Table 3.3, but:
• Each storey exit needs to be able to serve 240 people, because of discounting as described in paragraph 2.21. The minimum exit width needed for 240 people in Table 2.3 is 1200mm. As described in paragraph 3.10a, the stair should be at least as wide as the storey exit serving it.
• The required stair width is therefore 1200mm.

View this page on RegsUK