Section 3: Design for vertical escape Width of escape stairs
Width of escape stairs
3.10
The width of escape stairs should meet all of the following conditions.
3.11
Approved Document K requires stairs more than 2000mm wide in public buildings to have a central handrail.
3.12
If an exit route from a stair is also the escape route from the ground storey and/or basement storey, the width of the exit route may need to be increased (see paragraph 2.23).
Table 3.1 Minimum widths of escape stairs
| Situation of stair | Maximum number of people served(1) | Minimum stair width (mm) |
|---|---|---|
1a. In a ‘residential (institutional)’ building (unless the stair will only be used by staff) | 150 | 1000(2) |
1b. In an ‘assembly and recreation’ building and serving an area used for assembly purposes (unless the area is less than 100m²) | 220 | 1100 |
1c. In any other building and serving an area with an occupancy of more than 50 | Over 220 | See note 3 |
2. Any stair not described above | 50 | 800(4) |
NOTES:
Calculation of minimum stair width
3.13
The width depends on the number of stairs provided and the escape strategy (simultaneous or phased evacuation). If the maximum number of people needing to use escape stairs is unknown, calculate it using the floor space factors in Appendix D.
Discounting of stairs
3.14
Regardless of escape strategy, where two or more stairs are provided, it should be assumed that one might not be available during a fire. Each stair should be discounted in turn to ensure the capacity of the remaining stairs is adequate. This applies to buildings with or without a sprinkler system.
3.15
Paragraph 3.14 does not apply if either of the following applies.
Despite these exceptions, at least one storey exit still needs to be discounted (paragraph 2.21).
Paragraph 3.34 identifies cases where stairs need lobby protection.
Simultaneous evacuation
3.16
The width of escape stairs should take account of the number of people using them while evacuating all storeys at the same time. The following stairs should be designed to allow simultaneous evacuation.
Annexes B and C of BS 9999 include designs based on simultaneous evacuation.
3.17
The capacity of stairs of widths from 1000mm to 1800mm is given in Table 3.2.
Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building
| No. of floors served | Maximum number of people served by a stair of width: | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| 1000mm | 1100mm | 1200mm | 1300mm | 1400mm | 1500mm | 1600mm | 1700mm | 1800mm | |
| 1 | 150 | 220 | 240 | 260 | 280 | 300 | 320 | 340 | 360 |
| 2 | 190 | 260 | 285 | 310 | 335 | 360 | 385 | 410 | 435 |
| 3 | 230 | 300 | 330 | 360 | 390 | 420 | 450 | 480 | 510 |
| 4 | 270 | 340 | 375 | 410 | 445 | 480 | 515 | 550 | 585 |
| 5 | 310 | 380 | 420 | 460 | 500 | 540 | 580 | 620 | 660 |
| 6 | 350 | 420 | 465 | 510 | 555 | 600 | 645 | 690 | 735 |
| 7 | 390 | 460 | 510 | 560 | 610 | 660 | 710 | 760 | 810 |
| 8 | 430 | 500 | 555 | 610 | 665 | 720 | 775 | 830 | 885 |
| 9 | 470 | 540 | 600 | 660 | 720 | 780 | 840 | 900 | 960 |
| 10 | 510 | 580 | 645 | 710 | 775 | 840 | 905 | 970 | 1035 |
NOTES:
3.18
As an alternative to Table 3.2, the capacity of stairs 1100mm wide or wider can be found using either of the following formulas:
where:
P is the number of people that can be served
W is the width of the stair, in metres
N is the number of storeys served.
Separate calculations should be made for stairs serving basement storeys and stairs serving upper storeys.
The population, P, should be divided by the number of available stairs.
The formula is useful to determine the width of stairs where people are not distributed evenly – either within a storey or between storeys.
In the formula, 200W represents the number of people estimated to have left the stair after 2.5 minutes of evacuation, and 50 (W – 0.3)(N – 1) represents the number of people estimated to be on the stair after 2.5 minutes of evacuation.
Worked examples
Phased evacuation
3.19
Phased evacuation cannot be used in every type of building, but can be advantageous for escape stairs in high buildings. It requires supporting facilities, such as fire detection and alarm systems, to be provided and maintained.
In a phased evacuation, the first people to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, subsequent evacuation is done two floors at a time, reducing disruption in large buildings.
Phased evacuation enables stairs to be narrower than with simultaneous evacuation, and may be used for any building provided it is not identified in paragraph 3.16.
3.20
Phased evacuation in buildings with a storey over 30m in height introduces the potential for escaping people to impede firefighters entering and operating within the building. This can be addressed by consulting with the fire and rescue service about special management procedures.
In very tall buildings, typically with a storey over 45m in height, physical measures may need to be incorporated, such as by discounting a stair.
3.21
A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.
3.22
The minimum width of stairs needed for phased evacuation is given in Table 3.3.
Table 3.3 Minimum width of stairs designed for phased evacuation
| Maximum number of people in any storey | Stair width (mm) |
|---|---|
| 100 | 1000 |
| 120 | 1100 |
| 130 | 1200 |
| 140 | 1300 |
| 150 | 1400 |
| 160 | 1500 |
| 170 | 1600 |
| 180 | 1700 |
| 190 | 1800 |
NOTES:
Worked example using Table 3.3
What is the minimum width needed for the stairs serving a 15 storey office building (ground + 14 office floors), assuming a total population of 2500 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, three stairs are required.
The building is over 45m in height and designed for phased evacuation. It has been decided to discount one stair to take account of fire and rescue service operations as described in paragraph 3.20. Therefore:
Each remaining stair must be able to accommodate half the population of one storey (i.e. 90 people).
Thus each stair should be 1000mm wide (maximum capacity 100 people).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum width needed for 90 people in Table 2.3).
Additional worked example using Table 3.3
What is the minimum width needed for the stairs serving a 9 storey office building (ground + 8 office floors), assuming a total population of 1920 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, two stairs are required.
As both stairs need to be entered at each level through a protected lobby (see paragraph 3.21), both stairs can be assumed to be available (see paragraph 3.15). Therefore: