Escape route design Enclosure of corridors that are not protected corridors
Enclosure of corridors that are not protected corridors
2.25
If a corridor is used for a means of escape but is not a protected corridor, even though the enclosing partitions may have no fire resistance, both of the following should be met to inhibit the spread of smoke.
a. Partitions should continue to the soffit of the structural floor above, or to a suspended ceiling.
b. Openings into rooms from the corridor should be fitted with doors, which do not need to be fire doorsets.
Open planning will not inhibit the spread of smoke, but occupants can become aware of a fire quickly.