Design and protection of escape stairs External escape stairs

External escape stairs

3.31

Where a storey or part of the building has more than one escape route available, some of the escape routes may be via an external escape stair, provided the following conditions are met.

a. There is at least one internal escape stair from every part of each storey (excluding plant areas).
b. In the case of an ‘assembly and recreation’ (purpose group 5) building, the route is not intended for use by the public.
c. In the case of a ‘residential (institutional)’ (purpose group 2(a)) building, the route serves only office or residential staff accommodation.

3.32

Any external escape stair should meet all of the following conditions (Diagram 3.4).

a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape route from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting, in terms of integrity but not insulation (minimum E 30).

3.33

Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraphs 2.31 and 2.32.

Diagram 3.4 Fire resistance of areas near to external stairs

Diagram 3.4 Fire resistance of areas near to external stairs. Wording on the drawing: See para 3.32; Example a.; No fire resistance required for door; Fire resisting window (minimum RE 30); 1100mm above top landing; 1800mm; Fd; 1800mm; 9m below stair; 1800mm; fights and; Fd Fire doorset (minimum E 30); landings; Fd; Ground level or a roof or podium served by an independent stairway; Fire resisting construction (minimum RE 30); Example b.; 1100mm above top; landing; Fd 1800mm; 1800mm; 9m; below stair; fights and; Ground level or a roof or podium served by an independent stairway; landings; Section A–A Section B–B; A; 1800mm; B B NOTE: See para 3.31 on the provision of external stairs. See para 3.32d for weather Plan protection provisions. A; 1800mm
Diagram 3.4 Fire resistance of areas near to external stairs