Design and protection of escape stairs External walls adjacent to protected stairways

External walls adjacent to protected stairways

3.29

With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.3).

3.30

If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.

Diagram 3.3 External protection to protected stairways

Diagram 3.3 External protection to protected stairways. Wording on the drawing: See para 3.29; Configurations of stairs and external wall; Accommodation; Accommodation; Fire resisting construction 1800mm min. of adjacent building enclosure; Fire resisting construction of protected stairway; 1800mm min.; 1800mm min.; Stair; Stair; Non-fire resisting construction; Accommodation; Accommodation; Configuration A Configuration B
Diagram 3.3 External protection to protected stairways