Escape route design Inner rooms

Inner rooms

2.11

An inner room is at risk if a fire starts in the access room (Diagram 2.3). Such an arrangement should only be accepted if all of the following conditions are satisfied.

a. The occupant number of the inner room does not exceed:
i. 30 people for ‘residential (institutional)’ buildings (purpose group 2(a))
ii. 60 people for other purpose groups.
b. The inner room is not a bedroom.
c. The inner room is entered directly from the access room (but not via a corridor).
d. The escape route from the inner room does not pass through more than one access room.
e. The travel distance from any point in the inner room to the exits from the access room does not exceed the distances in Table 2.1.
f. The access room meets both of the following conditions.
i. It is not a place of special fire hazard.
ii. It is in the control of the same occupier.
g. One of the following arrangements is made.
i. The enclosures (walls or partitions) of the inner room stop a minimum of 500mm below the ceiling.
ii. The door or walls of the inner room contain a vision panel (minimum 0.1m2), so people can see if a fire starts in the access room.
iii. The access room is fitted with an automatic fire detection and alarm system to warn occupants of the inner room if a fire starts in the access room.

Diagram 2.3 Inner room and access room

Diagram 2.3 Inner room and access room. Wording on the drawing: See para 2.11; Arrangement A Arrangement B; Exit Exit; Access room; NOTES:; Room with Inner room; alternative; Arrangement A Needs no special provision.; exits; Arrangement B Should observe the inner room; provisions in paragraph 2.11.; Exit
Diagram 2.3 Inner room and access room