Escape route design Open spatial planning

Open spatial planning

2.13

Escape routes should not be within 4.5m of openings between floors, such as for an escalator, unless either of the following applies.

a. The direction of travel is away from the opening.
b. An alternative escape route does not pass within 4.5m of the open connection (Diagram 2.5).

Diagram 2.4 Exits in a central core

Diagram 2.4 Exits in a central core. Wording on the drawing: See para 2.12; A; A A; A; C Fda; NOTE: The doors at both ends of the area marked ‘S’ should be self-closing fire doorsets unless the area is sub-divided such that any fire in that area will not be able to prejudice both sections of corridor at the same time. If that area is a lift lobby, doors should be provided as shown in Figure 9 in BS 9999.; Fd; Fd; PS; L; A; L; Fd Fd; S; L; L Lift S Services, toilets, etc. Fd Self-closing E 20 Sa fire doorsets Possible alternative position for fire doorset Fda C Corridor o… which accommodation opens Protected stairway PS A Accommodation (e.g. oƒce space – indicative layout shown); L; PS; Fd; Fd; Fda C; A A; A
Diagram 2.4 Exits in a central core

Diagram 2.5 Open connections

Diagram 2.5 Open connections. Wording on the drawing: See para 2.13; C; Area within 4.5m of the opening Escape route; From A and B at least one direction of travel Exit is away from the opening. From C, where the initial direction of travel is towards the opening, one of the escape routes is not less than 4.5m from the opening.; 4.5m; Opening; A; B; Exit
Diagram 2.5 Open connections