Residential care homes Planning for progressive horizontal evacuation
Planning for progressive horizontal evacuation
2.35
The guidance below on PHE is for care homes where the provisions of the Firecode documents do not apply (see paragraph 0.10).
PHE requires areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors. Protected areas provide a place of relative safety, from which further evacuation can be made if necessary.
2.36
Each storey used for the care of residents should be divided by compartment walls into at least three protected areas. All floors should be compartment floors.
2.37
Every protected area should have a minimum of two exits to adjoining protected areas. Maximum travel distances within a protected area should be both of the following.
2.38
A fire in one protected area should not prevent occupants of other areas from reaching a final exit (Diagram 2.11). Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.
2.39
The number of residents’ beds in protected areas should be based on an assessment of both of the following.
The maximum number of residents’ beds in one protected area should not exceed 10, but may need to be lower depending on the assessment.
2.40
A protected area used for horizontal evacuation from an adjoining protected area should have a floor area able to accommodate its own occupants plus those from the largest adjoining protected area.
Diagram 2.11 Progressive horizontal evacuation in care homes