Section 2: Design for horizontal escape Residential care homes

Residential care homes

General provisions

2.33

The choice of fire safety strategy depends on the way a building is designed, furnished, staffed and managed, and on the level of dependency of the residents.

2.34

In care homes for the elderly, some or all residents are likely to need help to evacuate. Buildings should generally be designed for progressive horizontal evacuation (PHE) in accordance with paragraphs 2.35 to 2.46.

For other care home types, the most appropriate of either a PHE or simultaneous evacuation strategy should be identified. The approach adopted in the design of a building must be recorded and communicated to the building management team, who can adopt procedures compatible with the building design.

Planning for progressive horizontal evacuation

2.35

The guidance below on PHE is for care homes where the provisions of the Firecode documents do not apply (see paragraph 0.10).

PHE requires areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors. Protected areas provide a place of relative safety, from which further evacuation can be made if necessary.

2.36

Each storey used for the care of residents should be divided by compartment walls into at least three protected areas. All floors should be compartment floors.

2.37

Every protected area should have a minimum of two exits to adjoining protected areas. Maximum travel distances within a protected area should be both of the following.

a. To the exit to the adjoining protected area: as shown in Table 2.1.
b. From any point to a storey exit or a final exit: 64m.

2.38

A fire in one protected area should not prevent occupants of other areas from reaching a final exit (Diagram 2.11). Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.

2.39

The number of residents’ beds in protected areas should be based on an assessment of both of the following.

a. The number of staff likely to be available.
b. The level of assistance that residents may require.

The maximum number of residents’ beds in one protected area should not exceed 10, but may need to be lower depending on the assessment.

2.40

A protected area used for horizontal evacuation from an adjoining protected area should have a floor area able to accommodate its own occupants plus those from the largest adjoining protected area.

Diagram 2.11 Progressive horizontal evacuation in care homes

Diagram 2.11 Progressive horizontal evacuation in care homes. Wording on the drawing: See para 2.38; Escape route to adjacent compartment, storey exit or final exit Compartment wall; Fire doorset in compartment wall; NOTE: Bedrooms and all ancillary accommodation should be enclosed in fire resisting construction.; Exit; Exit
Diagram 2.11 Progressive horizontal evacuation in care homes

Fire detection and alarm

2.41

A fire detection and alarm system should be provided to L1 standard in accordance with BS 5839-1.

Bedrooms

2.42

Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30). Every corridor serving bedrooms should be a protected corridor (see paragraph 2.24).

2.43

Bedrooms should not contain more than one single or double bed.

NOTE: It is not the intention to separate couples who happen to live in a care home by recommending that they sleep in separate bedrooms or beds.

Ancillary accommodation

2.44

Ancillary accommodation such as all of the following should be enclosed by fire resisting construction (minimum REI 30).

a. Chemical stores.
b. Cleaners’ rooms.
c. Clothes storage.
d. Day rooms.
e. Smoking rooms.
f. Disposal rooms.
g. Plant rooms.
h. Linen stores.
i. Kitchens.
j. Laundry rooms.
k. Staff changing and locker rooms.
l. Store rooms.

Door closing devices

2.45

If doors fitted with a self-closing device could present an obstacle to residents, the following hardware in accordance with BS EN 1155 is appropriate.

a. Bedrooms: free-swing door closers.
b. Circulation spaces: hold-open devices.

Sprinkler systems

2.46

Care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E.