Pathways around fire-separating elements Protected escape routes

Protected escape routes

9.5

If the fire resisting construction of a protected escape route is either of the following.

a. Not carried to full storey height.
b. At the top storey, not carried to the underside of the roof covering.

Then the cavity above or below the fire resisting construction should be either of the following.

i. Fitted with cavity barriers on the line of the enclosure.
ii. For cavities above the fire resisting construction, enclosed on the lower side by a fire resisting ceiling (minimum EI 30) that extends throughout the building, compartment or separated part (see Diagram 9.3).