Section 9: Cavities Pathways around fire-separating elements
Pathways around fire-separating elements
Junctions and edges of cavities
9.3
Cavity barriers should be provided at all of the following locations.
This does not apply where a wall meets the conditions of Diagram 9.2.
9.4
It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should extend to the underside of the floor or roof above.
Protected escape routes
9.5
If the fire resisting construction of a protected escape route is either of the following.
Then the cavity above or below the fire resisting construction should be either of the following.
Cavities affecting alternative escape routes
9.6
In divided corridors, cavity barriers may be needed to prevent alternative escape routes being affected by fire and/or smoke (see paragraph 2.27 and Diagram 2.9).
Separation of bedrooms in ‘residential (institutional)’ and ‘residential (other)’ buildings
9.7
Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.
Double-skinned corrugated or profiled roof sheeting
9.8
Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting if the sheeting complies with all of the following.
Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting