Section 9: Cavities Pathways around fire-separating elements

Pathways around fire-separating elements

Junctions and edges of cavities

9.3

Cavity barriers should be provided at all of the following locations.

a. At the edges of cavities, including around openings (such as windows, doors and exit/entry points for services).
b. At the junction between an external cavity wall and every compartment floor and compartment wall.
c. At the junction between an internal cavity wall and every compartment floor, compartment wall or other wall or door assembly forming a fire resisting barrier.

This does not apply where a wall meets the conditions of Diagram 9.2.

9.4

It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should extend to the underside of the floor or roof above.

Protected escape routes

9.5

If the fire resisting construction of a protected escape route is either of the following.

a. Not carried to full storey height.
b. At the top storey, not carried to the underside of the roof covering.

Then the cavity above or below the fire resisting construction should be either of the following.

i. Fitted with cavity barriers on the line of the enclosure.
ii. For cavities above the fire resisting construction, enclosed on the lower side by a fire resisting ceiling (minimum EI 30) that extends throughout the building, compartment or separated part (see Diagram 9.3).

Cavities affecting alternative escape routes

9.6

In divided corridors, cavity barriers may be needed to prevent alternative escape routes being affected by fire and/or smoke (see paragraph 2.27 and Diagram 2.9).

Separation of bedrooms in ‘residential (institutional)’ and ‘residential (other)’ buildings

9.7

Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.

Double-skinned corrugated or profiled roof sheeting

9.8

Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting if the sheeting complies with all of the following.

a. The sheeting is rated class A2-s3, d2 or better.
b. Both surfaces of the insulating layer are rated class C-s3, d2 or better.
c. Both surfaces of the insulating layer make contact with the inner and outer skins of cladding (Diagram 9.4).

Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.2 Cavity walls excluded from provisions for cavity barriers. Wording on the drawing: See para 9.3; Close cavity at top of wall (unless cavity is totally filled with insulation); NOTES:; 1. Materials used to close the cavity in this arrangement do not need to achieve a specific performance in relation to fire resistance.; 2. Domestic meter cupboards may be installed provided that the following conditions are met: a. There are no more than two cupboards per dwelling b. The openings in the outer wall leaf are not bigger than; Opening; 800˜500mm for each cupboard c. The inner leaf is not penetrated except by a sleeve not; Close cavity around opening; more than 80˜80mm, which is fire-stopped.; Two leaves of brick or concrete each at least 75mm thick; 3. Materials achieving class B-s3, d2 or worse may be placed within the cavity.
Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.3 Fire resisting ceiling below cavity. Wording on the drawing: See para 9.5; Floor or roof above; NOTE: The ceiling should meet all of the following conditions. a. Provide a minimum fire resistance of EI 30. b. Be imperforate, except for an opening described in paragraph 9.17. c. Extend throughout the building or compartment. d. Not be easily demountable.; Cavity; Ceiling surface/product exposed to; cavity – class C-s3, d2 or better; Ceiling; So˜t of ceiling – class B-s3, d2 or better
Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting. Wording on the drawing: See para 9.8; Arrangement A Arrangement B; Acceptable without cavity barriers Cavity barriers necessary; Cavity barrier; Insulation; The insulation should make contact with both skins of sheeting. See also Diagram 8.2a regarding the need for fire-stopping where such roofs pass over the top of a compartment wall.
Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting