Methods for calculating acceptable unprotected area Sprinkler systems
Sprinkler systems
13.22
If a building is fitted throughout with a sprinkler system in accordance with Appendix E, either of the following is permitted.
a. The boundary distance can be halved, to a minimum distance of 1m.
b. The amount of unprotected area can be doubled.