Section 5: General provisions General provisions

General provisions

Headroom in escape routes

5.16

Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.

Flooring of escape routes

5.17

Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.

Ramps and sloping floors

5.18

A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.

5.19

Guidance for where there is fixed seating is given in both of the following.

a. Approved Documents K and M give guidance on the design of ramps and associated landings, and on aisles and gangways where there is fixed seating.
b. Section 2 of this document refers to Annex D of BS 9999, which gives guidance on the design of means of escape in places with fixed seating.

Final exits

5.20

The width of a final exit should be at least the same as the minimum required width of the escape route it serves.

5.21

People should be able to rapidly leave the area around the building. Direct access to a street, passageway, walkway or open space should be available. The route away from the building should comply with the following.

a. Be well defined.
b. If necessary, have suitable guarding.

5.22

Final exits should not present a barrier for disabled people. Where the route to a final exit does not include stairs, a level threshold and, where necessary, a ramp should be provided.

5.23

Final exit locations should be clearly visible and recognisable.

5.24

Final exits should avoid outlets of basement smoke vents and openings to transformer chambers, refuse chambers, boiler rooms and similar risks.

Table 5.1 Provisions for escape lighting

Use of the building or part of the buildingAreas requiring escape lighting
ResidentialAll common escape routes(1), except in two storey blocks of flats
Office, industrial, storage and other nonresidential
a. Underground or windowless accommodation
b. Stairs either:
• in a central core
• that serve storey(s) more than 18m above ground level
c. Internal corridors more than 30m long
d. Open-plan areas of more than 60m2
Shop and commercial, and car parks
a. Underground or windowless accommodation
b. Stairs either:
• in a central core
• that serve storey(s) more than 18m above ground level
c. Internal corridors more than 30m long
d. Open-plan areas of more than 60m2
e. All escape routes (other than the following exception) to which the public are admitted.(1) The exception is shops that meet all of the following:
• have a maximum of three storeys
• have no sales floor of more than 280m2
• are not a restaurant or bar
Assembly and recreation
a. All escape routes(1)
b. Accommodation except for that which is open on one side to view sport or entertainment during normal daylight hours
Any purpose group
a. All toilet accommodation with a minimum floor area of 8m2
b. Electricity and generator rooms
c. Switch room/battery room for emergency lighting system
d. Emergency control rooms

NOTE:

1. Including external escape routes.

Lighting of escape routes

5.25

All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the routes listed in Table 5.1.

5.26

Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.

5.27

Escape lighting should conform to BS 5266-1.

Exit signs

5.28

Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4.

Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.

Some buildings may require additional signs to comply with other legislation.

Protected power circuits

5.29

To limit potential damage to cables in protected circuits, all of the following should apply.

a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.

5.30

A protected circuit to operate equipment during a fire should achieve all of the following.

a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.

5.31

Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.