Final exits Table 5.1 Provisions for escape lighting

Table 5.1 Provisions for escape lighting

Use of the building or part of the buildingAreas requiring escape lighting
ResidentialAll common escape routes(1), except in two storey blocks of flats
Office, industrial, storage and other nonresidential
a. Underground or windowless accommodation
b. Stairs either:
• in a central core
• that serve storey(s) more than 18m above ground level
c. Internal corridors more than 30m long
d. Open-plan areas of more than 60m2
Shop and commercial, and car parks
a. Underground or windowless accommodation
b. Stairs either:
• in a central core
• that serve storey(s) more than 18m above ground level
c. Internal corridors more than 30m long
d. Open-plan areas of more than 60m2
e. All escape routes (other than the following exception) to which the public are admitted.(1) The exception is shops that meet all of the following:
• have a maximum of three storeys
• have no sales floor of more than 280m2
• are not a restaurant or bar
Assembly and recreation
a. All escape routes(1)
b. Accommodation except for that which is open on one side to view sport or entertainment during normal daylight hours
Any purpose group
a. All toilet accommodation with a minimum floor area of 8m2
b. Electricity and generator rooms
c. Switch room/battery room for emergency lighting system
d. Emergency control rooms

NOTE:

1. Including external escape routes.