Unprotected areas and fire resistance Small unprotected areas

Small unprotected areas

13.11

In an otherwise protected wall, small unprotected areas may be ignored where they meet the conditions in Diagram 13.5.

Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary

Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary. Wording on the drawing: See para 13.11; Roof; Roofs pitched at an angle of less than 70 degrees may be disregarded for a a separation distance purposes; b; b; a; b b; The unprotected area of the external wall of a stairway forming a protected shaft may be disregarded for separation distance purposes; b b; b a; Compartment; Compartment wall; floor; Dimensional restrictions; Represents an unprotected area of not more than 1m2 which may consist of two or more smaller areas within an area of 1000mm˜1000mm; a; 4000mm minimum distance; b; 1500mm minimum distance; Represents an area of not more than 0.1m2
Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary