Thatch and wood shingles Table 14.1 Limitations on roof coverings

Table 14.1 Limitations on roof coverings

Designation(1) of covering of roof or part of roofDistance from any point on relevant boundary
Less than 6mAt least 6mAt least 12mAt least 20m
BROOF(t4)●●●●
CROOF(t4)○●●●
DROOF(t4)○●(2)(3) ●(2) ●
EROOF(t4)○●(2)(3) ●(2) ●(2)
FROOF(t4)○○○●(2)(3)
● Acceptable. ○ Not acceptable.

NOTES:

Separation distances do not apply to enclosed/covered walkways. However, see Diagram 8.2 if the roof passes over the top of a compartment wall.

Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) classification.

1. The designation of external roof surfaces is explained in Appendix B
2. Not acceptable on any of the following buildings.
a. Industrial, storage or other non-residential purpose group (purpose groups 6 and 7) buildings of any size.
b. Any other buildings with a cubic capacity of more than 1500m3.
3. Acceptable on buildings not listed in (2) if both of the following apply.
a. Part of the roof has a maximum area of 3m2 and is a minimum of 1500mm from any similar part.
b. The roof between the parts is covered with a material rated class A2-s3, d2 or better.