Section 14: Resisting fire spread over roof coverings

Section 14: Resisting fire spread over roof coverings

Introduction

14.1

‘Roof covering’ describes one or more layers of material, but not the roof structure as a whole.

14.2

Provisions for the fire properties of roofs are given in other parts of this document.

a. Requirement B1 – for roofs that are part of a means of escape.
b. Requirement B2 – for the internal surfaces of rooflights as part of internal linings.
c. Requirement B3 – for roofs that are used as a floor and for roofs passing over a compartment wall.
d. Section 13 – the circumstances in which a roof is subject to the provisions for space separation.

Separation distances

14.3

Separation distance is the minimum distance from the roof, or part of the roof, to the relevant boundary (paragraph 13.5). Table 14.1 sets out separation distances by the type of roof covering and the size and use of the building.

In addition, roof covering products (and/or materials) defined in Commission Decision 2000/553/ EC of 6 September 2000, implementing Council Directive 89/106/EEC, can be considered to fulfil all of the requirements for the performance characteristic ‘external fire performance’ without the need for testing, provided that any national provisions on the design and execution of works are fulfilled, and can be used without restriction.

14.4

The performance of rooflights is specified in a similar way to the performance of roof coverings. Plastic rooflights may also be used.

Plastic rooflights

14.5

Table 14.2 and Diagram 14.1 set the limitations for using plastic rooflights whose lower surface has a minimum rating of class D-s3, d2.

14.6

Table 14.3 sets the limitations for using thermoplastic materials with a TP(a) rigid or TP(b) (see also Diagram 14.1) classification. The method of classifying thermoplastic materials is given in Appendix B.

14.7

Other than for the purposes of Diagram 8.2, polycarbonate or uPVC rooflights achieving a minimum rating of class C-s3, d2 can be regarded as having a BROOF(t4) classification.

Unwired glass in rooflights

14.8

When used in rooflights, unwired glass a minimum of 4mm thick can be regarded as having a BROOF(t4) classification.

Thatch and wood shingles

14.9

If the performance of thatch or wood shingles cannot be established, they should be regarded as having an EROOF(t4) classification in Table 14.1.

Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface

Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface. Wording on the drawing: See paras 14.5 and 14.6; Rooflight* max. area 5m2; * Or group of rooflights amounting to no more than 5m2 † Class D-s3, d2 rooflights to rooms in industrial and other; non-residential purpose groups may be spaced 1800mm apart provided the rooflights are evenly distributed and do not exceed 20% of the area of the room; 3m† minimum between any two rooflights in any direction; NOTES:; 1. There are restrictions on the use of plastic rooflights in the guidance to requirement B2 in Section 6.; Rooflight* max. area 5m2; 2. Surrounding roof covering to be class B-s3, d2 for at least 3m distance.; 3. Where Diagram 8.2a or 8.2b applies, rooflights should be at least 1500mm from the compartment wall.
Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface

Table 14.1 Limitations on roof coverings

Designation(1) of covering of roof or part of roofDistance from any point on relevant boundary
Less than 6mAt least 6mAt least 12mAt least 20m
BROOF(t4)●●●●
CROOF(t4)○●●●
DROOF(t4)○●(2)(3) ●(2) ●
EROOF(t4)○●(2)(3) ●(2) ●(2)
FROOF(t4)○○○●(2)(3)
● Acceptable. ○ Not acceptable.

NOTES:

Separation distances do not apply to enclosed/covered walkways. However, see Diagram 8.2 if the roof passes over the top of a compartment wall.

Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) classification.

1. The designation of external roof surfaces is explained in Appendix B
2. Not acceptable on any of the following buildings.
a. Industrial, storage or other non-residential purpose group (purpose groups 6 and 7) buildings of any size.
b. Any other buildings with a cubic capacity of more than 1500m3.
3. Acceptable on buildings not listed in (2) if both of the following apply.
a. Part of the roof has a maximum area of 3m2 and is a minimum of 1500mm from any similar part.
b. The roof between the parts is covered with a material rated class A2-s3, d2 or better.

Table 14.2 Class D-s3, d2 plastic rooflights: limitations on use and boundary distance

Minimum classification on lower surface(1) Space that rooflight can serveMinimum distance from any point on relevant boundary to rooflight with an external designation(2) of:
EROOF(t4) or DROOF(t4)FROOF(t4)
Class D-s3, d2
a. Balcony, verandah, carport, covered way or loading bay that has at least one longer side wholly or permanently open
b. Detached swimming pool
c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2
6m20m
d. Circulation space(3) (except a protected stairway)
e. Room(3)
6m(4) 20m(4)

NOTES:

None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test (see paragraph 14.7) may be regarded as having a BROOF(t4) classification. Where Diagram 8.2a or 8.2b applies, rooflights should be a minimum of 1500m from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.

1. See also the guidance to requirement B2 in Section 6.
2. The designation of external roof surfaces is explained in Appendix B.
3. Single-skinned rooflight only, in the case of non-thermoplastic material.
4. The rooflight should also meet the provisions of Diagram 14.1.

Table 14.3 TP(a) and TP(b) thermoplastic rooflights: limitations on use and boundary distance

Minimum classification on lower surface(1) Space that rooflight can serveMinimum distance from any point on relevant boundary to rooflight with an external surface classification(1) of:
TP(a)TP(b)
1. TP(a) rigid
Any space except a protected stairway6m(2) Not applicable
2. TP(b)
a. Balcony, verandah, carport, covered way or loading bay, which has at least one longer side wholly or permanently open
b. Detached swimming pool
c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2
Not applicable6m
d. Circulation space(3) (except a protected stairway)
e. Room(3)
Not applicable6m(4)

NOTES:

None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) designation. Where Diagram 8.2a or 8.2b applies, rooflights should be at least 1500mm from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.

1. See also the guidance to requirement B2 in Section 6.
2. No limit in the case of any space described in 2(a), (b) and (c).
3. Single-skinned rooflight only, in the case of non-thermoplastic material.
4. The rooflight should also meet the provisions of Diagram 14.1.