Separation distances Thatch and wood shingles

Thatch and wood shingles

14.9

If the performance of thatch or wood shingles cannot be established, they should be regarded as having an EROOF(t4) classification in Table 14.1.

Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface

Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface. Wording on the drawing: See paras 14.5 and 14.6; Rooflight* max. area 5m2; * Or group of rooflights amounting to no more than 5m2 † Class D-s3, d2 rooflights to rooms in industrial and other; non-residential purpose groups may be spaced 1800mm apart provided the rooflights are evenly distributed and do not exceed 20% of the area of the room; 3m† minimum between any two rooflights in any direction; NOTES:; 1. There are restrictions on the use of plastic rooflights in the guidance to requirement B2 in Section 6.; Rooflight* max. area 5m2; 2. Surrounding roof covering to be class B-s3, d2 for at least 3m distance.; 3. Where Diagram 8.2a or 8.2b applies, rooflights should be at least 1500mm from the compartment wall.
Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface

Table 14.1 Limitations on roof coverings

Designation(1) of covering of roof or part of roofDistance from any point on relevant boundary
Less than 6mAt least 6mAt least 12mAt least 20m
BROOF(t4)●●●●
CROOF(t4)○●●●
DROOF(t4)○●(2)(3) ●(2) ●
EROOF(t4)○●(2)(3) ●(2) ●(2)
FROOF(t4)○○○●(2)(3)
● Acceptable. ○ Not acceptable.

NOTES:

Separation distances do not apply to enclosed/covered walkways. However, see Diagram 8.2 if the roof passes over the top of a compartment wall.

Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) classification.

1. The designation of external roof surfaces is explained in Appendix B
2. Not acceptable on any of the following buildings.
a. Industrial, storage or other non-residential purpose group (purpose groups 6 and 7) buildings of any size.
b. Any other buildings with a cubic capacity of more than 1500m3.
3. Acceptable on buildings not listed in (2) if both of the following apply.
a. Part of the roof has a maximum area of 3m2 and is a minimum of 1500mm from any similar part.
b. The roof between the parts is covered with a material rated class A2-s3, d2 or better.

Table 14.2 Class D-s3, d2 plastic rooflights: limitations on use and boundary distance

Minimum classification on lower surface(1) Space that rooflight can serveMinimum distance from any point on relevant boundary to rooflight with an external designation(2) of:
EROOF(t4) or DROOF(t4)FROOF(t4)
Class D-s3, d2
a. Balcony, verandah, carport, covered way or loading bay that has at least one longer side wholly or permanently open
b. Detached swimming pool
c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2
6m20m
d. Circulation space(3) (except a protected stairway)
e. Room(3)
6m(4) 20m(4)

NOTES:

None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test (see paragraph 14.7) may be regarded as having a BROOF(t4) classification. Where Diagram 8.2a or 8.2b applies, rooflights should be a minimum of 1500m from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.

1. See also the guidance to requirement B2 in Section 6.
2. The designation of external roof surfaces is explained in Appendix B.
3. Single-skinned rooflight only, in the case of non-thermoplastic material.
4. The rooflight should also meet the provisions of Diagram 14.1.

Table 14.3 TP(a) and TP(b) thermoplastic rooflights: limitations on use and boundary distance

Minimum classification on lower surface(1) Space that rooflight can serveMinimum distance from any point on relevant boundary to rooflight with an external surface classification(1) of:
TP(a)TP(b)
1. TP(a) rigid
Any space except a protected stairway6m(2) Not applicable
2. TP(b)
a. Balcony, verandah, carport, covered way or loading bay, which has at least one longer side wholly or permanently open
b. Detached swimming pool
c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2
Not applicable6m
d. Circulation space(3) (except a protected stairway)
e. Room(3)
Not applicable6m(4)

NOTES:

None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) designation. Where Diagram 8.2a or 8.2b applies, rooflights should be at least 1500mm from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.

1. See also the guidance to requirement B2 in Section 6.
2. No limit in the case of any space described in 2(a), (b) and (c).
3. Single-skinned rooflight only, in the case of non-thermoplastic material.
4. The rooflight should also meet the provisions of Diagram 14.1.