Thatch and wood shingles Table 14.3 TP(a) and TP(b) thermoplastic rooflights: limitations on use and boundary distance
Table 14.3 TP(a) and TP(b) thermoplastic rooflights: limitations on use and boundary distance
| Minimum classification on lower surface(1) | Space that rooflight can serve | Minimum distance from any point on relevant boundary to rooflight with an external surface classification(1) of: | |
|---|---|---|---|
| TP(a) | TP(b) | ||
1. TP(a) rigid | Any space except a protected stairway | 6m(2) | Not applicable |
2. TP(b) | a. Balcony, verandah, carport, covered way or loading bay, which has at least one longer side wholly or permanently open b. Detached swimming pool c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2 | Not applicable | 6m |
d. Circulation space(3) (except a protected stairway) e. Room(3) | Not applicable | 6m(4) | |
NOTES:
None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) designation. Where Diagram 8.2a or 8.2b applies, rooflights should be at least 1500mm from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.
1. See also the guidance to requirement B2 in Section 6.
2. No limit in the case of any space described in 2(a), (b) and (c).
3. Single-skinned rooflight only, in the case of non-thermoplastic material.
4. The rooflight should also meet the provisions of Diagram 14.1.