Width of escape stairs Table 3.1 Minimum widths of escape stairs

Table 3.1 Minimum widths of escape stairs

Situation of stairMaximum number of people served(1) Minimum stair width (mm)
1a. In a ‘residential (institutional)’ building (unless the stair will only be used by staff)
1501000(2)
1b. In an ‘assembly and recreation’ building and serving an area used for assembly purposes (unless the area is less than 100m²)
2201100
1c. In any other building and serving an area with an occupancy of more than 50
Over 220See note 3
2. Any stair not described above
50800(4)

NOTES:

1. Assessed as likely to use the stair in a fire emergency.
2. Section 6 of BS 9999 recommends that firefighting stairs should be at least 1100mm wide.
3. See Table 3.2 for the size of stairs for simultaneous evacuation, and Table 3.3 for phased evacuation.
4. To comply with the guidance in Approved Document M on minimum widths for areas accessible to disabled people, this may need to be increased to 1000mm.