Fire resistance (2029 amendment) Table B2 Minimum periods of fire resistance (2029 amendment)

Table B2 Minimum periods of fire resistance (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B2 Minimum periods of fire resistance.

Purpose group of buildingMinimum periods of fire resistance(1) (minutes) in a:
Basement storey* including floor overGround or upper storey
Depth (m) of the lowest basementHeight (m) of top floor above ground, in a building or separated part of a building
More than 10Up to 10Up to 5Up to 11Up to 18Up to 30More than 30
1. Residential:
a. Block of flats
– without sprinkler system90 min60 min30 min† 60 min+§ Not permitted(2) Not permitted(2) Not permitted(2)
– with sprinkler system(3) 90 min60 min30 min† 60 min+§ 60 min+§ 90 min+120 min+
b. and c. Dwellinghouse
Not applicable(4) 30 min*† 30 min† 60 min(5) 60 min(5) Not applicable(4) Not applicable(4)
2. Residential
a. Institutional
90 min60 min30 min† 60 min60 min90 min120 min‡
b. Other residential
90 min60 min30 min† 60 min60 min90 min120 min‡
3. Office:
– without sprinkler system90 min60 min30 min† 60 min60 min90 minNot permitted(6)
– with sprinkler system(3) 60 min60 min30 min† 30 min† 30 min† 60 min120 min‡
4. Shop and commercial:
– without sprinkler system90 min60 min60 min60 min60 min90 minNot permitted(6)
– with sprinkler system(3) 60 min60 min30 min† 60 min60 min60 min120 min‡
5. Assembly and recreation:
– without sprinkler system90 min60 min60 min60 min60 min90 minNot permitted(6)
– with sprinkler system(3) 60 min60 min30 min† 60 min60 min60 min120 min‡
6. Industrial:
– without sprinkler system120 min90 min60 min90 min90 min120 minNot permitted(6)
– with sprinkler system(3) 90 min60 min30 min† 60 min60 min90 min120 min‡
7. Storage and other nonresidential:
a. any building or part not described elsewhere:
– without sprinkler system120 min90 min60 min90 min90 min120 minNot permitted(6)
– with sprinkler system(3) 90 min60 min30 min† 60 min60 min90 min120 min‡
b. car park for light vehicles:
i. open sided car park(7) Not applicable
Not applicable15 min†# 15 min†#(8) 15 min†#(8) 15 min†#(8) 60 min
ii. any other car park 90 min
60 min30 min† 60 min60 min90 min120 min‡

NOTES:

For single storey buildings, the periods under the heading ‘Up to 5’ apply. If single storey buildings have basements, for the basement storeys the period appropriate to their depth applies.

* For the floor over a basement or, if there is more than one basement, the floor over the topmost basement, the higher of the period for the basement storey and the period for the ground or upper storey applies.

† For compartment walls that separate buildings, the period is increased to a minimum of 60 minutes.

+ For any floor that does not contribute to the support of the building within a flat of more than one storey, the period is reduced to 30 minutes.

§ For flat conversions, refer to paragraphs 6.5 to 6.7 of Approved Document B Volume 1 regarding the acceptability of 30 minutes.

‡ For elements that do not form part of the structural frame, the period is reduced to 90 minutes.

# For elements that protect the means of escape, the period is increased to 30 minutes.

1. Refer to note 1, Table B1 for the specific provisions of test.
2. Blocks of flats with a top storey more than 11m above ground level (see Diagram D6) should be fitted with a sprinkler system in accordance with Appendix E.
NOTE: Sprinklers should be provided within the individual flats, they do not need to be provided in the common areas such as stairs, corridors or landings when these areas are fire sterile.
3. ‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.
4. Very large (with a top storey more than 18m above ground level or with a 10m deep basement) or unusual dwellinghouses are outside the scope of the guidance provided with regard to dwellinghouses.
5. A minimum of 30 minutes in the case of three storey dwellinghouses, increased to 60 minutes minimum for compartment walls separating buildings.
6. Buildings within the ‘office’, ‘shop and commercial’, ‘assembly and recreation’, ‘industrial’ and ‘storage and other non-residential’ (except car parks for light vehicles) purpose groups (purpose groups 3 to 7(a)) require sprinklers where there is a top storey more than 30m above ground level.
7. The car park should comply with the relevant provisions in the guidance on requirement B3, Section 11.
8. For the purposes of meeting the Building Regulations, the following types of steel elements are deemed to have satisfied the minimum period of fire resistance of 15 minutes when tested to the European test method.
i. Beams supporting concrete floors, maximum Hp/A=230m-1 operating under full design load.
ii. Free-standing columns, maximum Hp/A=180m-1 operating under full design load.
iii. Wind bracing and struts, maximum Hp/A=210m-1 operating under full design load.
Guidance is also available in BS EN 1993-1-2.