Appendix B: Performance of materials, products and structures (2029 amendment) Fire resistance (2029 amendment)

Fire resistance (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Fire resistance.

B18 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B18.

Common to all of the provisions of Part B of the Building Regulations is the property of fire resistance. Fire resistance is a measure of one or more of the following criteria.

a. Resistance to collapse (loadbearing capacity), which applies to loadbearing elements only, denoted R in the European classification of the resistance to fire performance.
b. Resistance to fire penetration (integrity), denoted E in the European classification of the resistance to fire performance.
c. Resistance to the transfer of excessive heat (insulation), denoted I in the European classification of the resistance to fire performance.

B19 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B19.

The standards of fire resistance necessary for a particular building are based on assumptions about the severity of fires and the consequences should an element fail. Fire severity is estimated in very broad terms from the use of the building (its purpose group), on the assumption that the building contents (which constitute the fire load) are similar for buildings with the same use.

B20 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B20.

Because the use of buildings may change, a precise estimate of fire severity based on the fire load due to a particular use may be misleading. Therefore if a fire engineering approach of this kind is adopted, the likelihood that the fire load may change in the future needs to be considered.

B21 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B21.

Performance in terms of the fire resistance to be achieved by elements of structure, doors and other forms of construction is classified in accordance with one of the following.

a. BS EN 13501-2.
b. BS EN 13501-3.
c. BS EN 13501-4.

B22 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B22.

Fire resistance is measured in minutes. This relates to time elapsed in a standard test and should not be confused with real time.

B23 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B23.

The fire resistance necessary for different circumstances is set out in the following tables.

a. Table B1 gives the specific requirements for each element of structure.
b. Table B2 sets out the minimum periods of fire resistance for elements of structure.
c. Table B3 sets out limitations on the use of uninsulated fire resisting glazed elements.

B24 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B24.

This document uses the European classification system (REI) for fire resistance set out in BS EN 13501-2 to 4. Fire resistance is expressed as REI X, where X is the period of fire resistance in minutes in terms of loadbearing capacity (R), integrity (E) and insulation (I). Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.

B25 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B25.

Products or systems achieving the European classification (REI) should be specified wherever possible. However, there may be some products or systems that have been assessed as being capable of meeting a fire resistance performance classification. When assessed, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of loadbearing capacity, integrity and insulation based on the recommendations of paragraphs B1 to B5. In those situations, the performance classifications given in Table B1 and Table B2 may be used.

Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B1 Specific provisions of the test for fire resistance of elements of structure, etc..

Part of buildingMinimum provisions when tested and classified to the relevant European standard (minutes)(1) or assessed following the recommendations of paragraphs B1 to B5 (minutes)(2) Type of exposure
Loadbearing capacity(3) IntegrityInsulation
1. Structural frame, beam or column.
See Table B2Not applicableNot applicableExposed faces
2. Loadbearing wall
(for a wall which is also described in any of the following items, the more onerous guidance should be applied).
See Table B2Not applicableNot applicableEach side separately
3. Floors(4)
a. between a shop and flat above
60 min or see Table B2 (whichever is greater)60 min or see Table B2 (whichever is greater)60 min or see Table B2 (whichever is greater)From underside(5)
b. in upper storey of two storey dwellinghouse (but not over garage or basement)
30 min15 min15 minFrom underside (5)
c. any other floor – including compartment floors.
See Table B2See Table B2See Table B2From underside (5)
4. Roofs
a. any part forming an escape route
30 min30 min30 minFrom underside (5)
b. any roof that performs the function of a floor.
See Table B2See Table B2See Table B2From underside (5)
5. External walls
a. any part a maximum of 1000mm from any point on the relevant boundary(6)
See Table B2See Table B2See Table B2Each side separately
b. any part a minimum of 1000mm from the relevant boundary(6)
See Table B2See Table B215 minFrom inside the building
c. any part beside an external escape route (Section 2, Diagram 2.7 of Approved Document B Volume 1 and Section 3, Diagram 3.4).
30 min30 minNo provision(7) (8) From inside the building
6. Compartment walls Separating either:
a. a flat from any other part of the building (see paragraph 7.1 of Approved Document B Volume 1)
60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)Each side separately
b. occupancies.
60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)60 min or see Table B2 (whichever is less)Each side separately
7. Compartment walls (other than in item 6 or item 10).
See Table B2See Table B2See Table B2Each side separately
8. Protected shafts
Excluding any firefighting shaft:
a. any glazing described in Section 8, Diagram 8.4
Not applicable30 minNo provision(8) Each side separately
b. any other part between the shaft and a protected lobby/corridor described in Section 8, Diagram 8.4
30 min30 min30 minEach side separately
c. any part not described in (a) or (b) above.
See Table B2See Table B2See Table B2Each side separately
9. Enclosure (that does not form part of a compartment wall or a protected shaft) to a:
a. protected stairway
30 min30 min30 min(8) Each side separately
b. lift shaft.
30 min30 min30 minEach side separately
10. Wall or floor separating an attached or integral garage from a dwellinghouse
30 min30 min30 min(8) From garage side
11. Fire resisting construction in dwellinghouses not described elsewhere
30 min30 min30 min(8) Each side separately
12. Firefighting shafts
120 min120 min120 minFrom side remote from shaft
a. construction that separates firefighting shaft from rest of building
60 min60 min60 minFrom shaft side
b. construction that separates firefighting stair, firefighting lift shaft and firefighting lobby.
60 min60 min60 minEach side separately
13. Enclosure (that is not a compartment wall or described in item 8) to a:
a. protected lobby
30 min30 min30 min(8) Each side separately
b. protected corridor.
30 min30 min30 min(8) Each side separately
14. Sub-division of a corridor
30 min30 min30 min(8) Each side separately
15. Fire resisting construction
a. construction that encloses places of special fire hazard
30 min30 min30 minEach side separately
b. construction between store rooms and sales area in shops
30 min30 min30 minEach side separately
c. fire resisting sub-division
30 min30 min30 minEach side separately
d. construction that encloses bedrooms and ancillary accommodation in care homes.
30 min30 min30 minEach side separately
16. Enclosure in a flat to a protected entrance hall, or to a protected landing.
30 min30 min30 min(8) Each side separately
17. Cavity barrier
Not applicable30 min15 minEach side separately
18. Ceiling see see paragraph 2.5, Diagram 2.3 of Approved Document B Volume 1 and paragraph 9.5 and Diagram 9.3.
Not applicable30 min30 minFrom underside
19. Duct described in paragraph 9.17e.
Not applicable30 minNo provisionFrom outside
20. Casing around a drainage system described in Diagram 9.1 of Approved Document B Volume 1.
Not applicable30 minNo provisionFrom outside
21. Flue walls described in Diagram 10.4.
Not applicableHalf the period given in Table B2 for the compartment wall/floorHalf the period given in Table B2 for the compartment wall/floorFrom outside
22. Construction described in note
(a) to paragraph 12.9 of Approved Document B Volume 1.
Not applicable30 min30 minFrom underside
23. Fire doorsets
See Table C1See Appendix C

NOTES:

1. Classified in accordance with BS EN 13501-2, BS EN 13501-3 or BS EN 13501-4. In the European classification ‘R’ is the resistance to fire in terms of loadbearing capacity, ‘E’ is the resistance to fire in terms of integrity, ‘I’ is the resistance to fire in terms of insulation. Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.
2. When assessed as being capable of meeting a performance classification, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of loadbearing capacity, integrity or insulation for a period of minutes, when following the recommendations of paragraphs B1 to B5.
3. Applies to loadbearing elements only (see paragraph B18).
4. Guidance on increasing the fire resistance of existing timber floors is given in BRE Digest 208.
5. Only if a suspended ceiling meets the appropriate provisions should it be relied on to add to the fire resistance of the floor.
6. Such walls may contain areas that do not need to be fire resisting (unprotected areas). See Section 13.
7. Unless needed as part of a wall in item 5a or 5b.
8. Except for any limitations on uninsulated glazed elements given in Table B3.

Table B2 Minimum periods of fire resistance (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B2 Minimum periods of fire resistance.

Purpose group of buildingMinimum periods of fire resistance(1) (minutes) in a:
Basement storey* including floor overGround or upper storey
Depth (m) of the lowest basementHeight (m) of top floor above ground, in a building or separated part of a building
More than 10Up to 10Up to 5Up to 11Up to 18Up to 30More than 30
1. Residential:
a. Block of flats
– without sprinkler system90 min60 min30 min† 60 min+§ Not permitted(2) Not permitted(2) Not permitted(2)
– with sprinkler system(3) 90 min60 min30 min† 60 min+§ 60 min+§ 90 min+120 min+
b. and c. Dwellinghouse
Not applicable(4) 30 min*† 30 min† 60 min(5) 60 min(5) Not applicable(4) Not applicable(4)
2. Residential
a. Institutional
90 min60 min30 min† 60 min60 min90 min120 min‡
b. Other residential
90 min60 min30 min† 60 min60 min90 min120 min‡
3. Office:
– without sprinkler system90 min60 min30 min† 60 min60 min90 minNot permitted(6)
– with sprinkler system(3) 60 min60 min30 min† 30 min† 30 min† 60 min120 min‡
4. Shop and commercial:
– without sprinkler system90 min60 min60 min60 min60 min90 minNot permitted(6)
– with sprinkler system(3) 60 min60 min30 min† 60 min60 min60 min120 min‡
5. Assembly and recreation:
– without sprinkler system90 min60 min60 min60 min60 min90 minNot permitted(6)
– with sprinkler system(3) 60 min60 min30 min† 60 min60 min60 min120 min‡
6. Industrial:
– without sprinkler system120 min90 min60 min90 min90 min120 minNot permitted(6)
– with sprinkler system(3) 90 min60 min30 min† 60 min60 min90 min120 min‡
7. Storage and other nonresidential:
a. any building or part not described elsewhere:
– without sprinkler system120 min90 min60 min90 min90 min120 minNot permitted(6)
– with sprinkler system(3) 90 min60 min30 min† 60 min60 min90 min120 min‡
b. car park for light vehicles:
i. open sided car park(7) Not applicable
Not applicable15 min†# 15 min†#(8) 15 min†#(8) 15 min†#(8) 60 min
ii. any other car park 90 min
60 min30 min† 60 min60 min90 min120 min‡

NOTES:

For single storey buildings, the periods under the heading ‘Up to 5’ apply. If single storey buildings have basements, for the basement storeys the period appropriate to their depth applies.

* For the floor over a basement or, if there is more than one basement, the floor over the topmost basement, the higher of the period for the basement storey and the period for the ground or upper storey applies.

† For compartment walls that separate buildings, the period is increased to a minimum of 60 minutes.

+ For any floor that does not contribute to the support of the building within a flat of more than one storey, the period is reduced to 30 minutes.

§ For flat conversions, refer to paragraphs 6.5 to 6.7 of Approved Document B Volume 1 regarding the acceptability of 30 minutes.

‡ For elements that do not form part of the structural frame, the period is reduced to 90 minutes.

# For elements that protect the means of escape, the period is increased to 30 minutes.

1. Refer to note 1, Table B1 for the specific provisions of test.
2. Blocks of flats with a top storey more than 11m above ground level (see Diagram D6) should be fitted with a sprinkler system in accordance with Appendix E.
NOTE: Sprinklers should be provided within the individual flats, they do not need to be provided in the common areas such as stairs, corridors or landings when these areas are fire sterile.
3. ‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.
4. Very large (with a top storey more than 18m above ground level or with a 10m deep basement) or unusual dwellinghouses are outside the scope of the guidance provided with regard to dwellinghouses.
5. A minimum of 30 minutes in the case of three storey dwellinghouses, increased to 60 minutes minimum for compartment walls separating buildings.
6. Buildings within the ‘office’, ‘shop and commercial’, ‘assembly and recreation’, ‘industrial’ and ‘storage and other non-residential’ (except car parks for light vehicles) purpose groups (purpose groups 3 to 7(a)) require sprinklers where there is a top storey more than 30m above ground level.
7. The car park should comply with the relevant provisions in the guidance on requirement B3, Section 11.
8. For the purposes of meeting the Building Regulations, the following types of steel elements are deemed to have satisfied the minimum period of fire resistance of 15 minutes when tested to the European test method.
i. Beams supporting concrete floors, maximum Hp/A=230m-1 operating under full design load.
ii. Free-standing columns, maximum Hp/A=180m-1 operating under full design load.
iii. Wind bracing and struts, maximum Hp/A=210m-1 operating under full design load.
Guidance is also available in BS EN 1993-1-2.