Appendix C: Fire doorsets Table C1 Provisions for fire doorsets
Table C1 Provisions for fire doorsets
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table C1 Provisions for fire doorsets (2029 amendment).
| Position of door | Minimum fire resistance of door in terms of integrity (minutes) when tested to the relevant European standard(1) | Minimum fire resistance of door in terms of integrity (minutes) when tested to BS 476-22 |
|---|---|---|
1. In a compartment wall separating buildings | Same as for the wall in which the door is fitted, but a minimum of 60 minutes | Same as for the wall in which the door is fitted, but a minimum of 60 minutes |
2. In a compartment wall: | ||
a. if it separates a flat from a space in common use | E 30 Sa(2) | FD 30 S(2) |
b. enclosing a protected shaft forming a stairway or an evacuation shaft wholly or partly above the adjoining ground in a building used for flats, other residential, assembly and recreation, or office purposes | E 30 Sa(2) | FD 30 S(2) |
c. enclosing a protected shaft forming a stairway or an evacuation shaft not described in (b) above | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(2) | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix S(2) |
d. enclosing a protected shaft forming a lift or service shaft | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum |
e. not described in (a), (b), (c) or (d) above. | Same as for the wall in which it is fitted, but add Sa(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1 | Same as for the wall in which it is fitted, but add S(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1 |
3. In a compartment floor | Same as for the floor in which it is fitted | Same as for the floor in which it is fitted |
4. Forming part of the enclosures of: | ||
a. protected stairway or evacuation shaft (except as described in item 9 or 11(b) below) | E 30 Sa (2) | FD 30 S(2) |
b. a lift shaft (see paragraph 5.34(b) that does not form a protected shaft in 2(b), (c) or (d) above. | E 30 | FD 30 |
5. Forming part of the enclosure of: | ||
a. a protected lobby approach (or protected corridor) to a stairway or an evacuation shaft | E 30 Sa (2) | FD 30 S(2) |
b. any other protected corridor | E 20 Sa (2) | FD 20 S(2) |
c. a protected lobby approach to a lift shaft (paragraphs 5.37 to 5.39). | E 30 Sa (2) | FD 30 S(2) |
6. Giving access to an external escape route | E 30 | FD 30 |
7. Sub-dividing: | ||
a. corridors connecting alternative exits | E 20 Sa (2) | FD 20 S(2) |
b. dead-end portions of corridors from the remainder of the corridor. | E 20 Sa (2) | FD 20 S(2) |
8. Any door within a cavity barrier | E 30 | FD 30 |
9. Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat | E 20 | FD 20 |
10. Any door that forms part of the enclosure: | ||
a. to a place of special fire hazard | E 30 | FD 30 |
b. to ancillary accommodation in care homes (see paragraph 2.4). | E 30 | FD 30 |
11. In a dwellinghouse: | ||
a. between a dwellinghouse and a garage | E 30 Sa (2) | FD 30 S(2) |
b. forming part of the enclosures to a protected stairway in a single family dwellinghouse | E 20 | FD 20 |
c. within any fire resisting construction in a dwellinghouse not described elsewhere in this table. | E 20 | FD 20 |
NOTES:
1. Classified in accordance with BS EN 13501-2. National classifications do not necessarily equate with European classifications, therefore products cannot typically assume a European class unless they have been tested accordingly.
2. Unless pressurisation techniques that comply with BS EN 12101-6 are used, these doors should also comply with one of the following conditions.
a. Have a leakage rate not exceeding 3m3/m/hour (from head and jambs only) when tested at 25Pa under BS 476-31.1.
b. Meet the additional Sa classification when tested to BS EN 1634-3.