Appendix C: Fire doorsets Table C1 Provisions for fire doorsets

Table C1 Provisions for fire doorsets

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table C1 Provisions for fire doorsets (2029 amendment).

Position of doorMinimum fire resistance of door in terms of integrity (minutes) when tested to the relevant European standard(1) Minimum fire resistance of door in terms of integrity (minutes) when tested to BS 476-22
1. In a compartment wall separating buildings
Same as for the wall in which the door is fitted, but a minimum of 60 minutesSame as for the wall in which the door is fitted, but a minimum of 60 minutes
2. In a compartment wall:
a. if it separates a flat from a space in common use
E 30 Sa(2) FD 30 S(2)
b. enclosing a protected shaft forming a stairway or an evacuation shaft wholly or partly above the adjoining ground in a building used for flats, other residential, assembly and recreation, or office purposes
E 30 Sa(2) FD 30 S(2)
c. enclosing a protected shaft forming a stairway or an evacuation shaft not described in (b) above
Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(2) Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix S(2)
d. enclosing a protected shaft forming a lift or service shaft
Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimumHalf the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum
e. not described in (a), (b), (c) or (d) above.
Same as for the wall in which it is fitted, but add Sa(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1Same as for the wall in which it is fitted, but add S(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1
3. In a compartment floor
Same as for the floor in which it is fittedSame as for the floor in which it is fitted
4. Forming part of the enclosures of:
a. protected stairway or evacuation shaft (except as described in item 9 or 11(b) below)
E 30 Sa (2) FD 30 S(2)
b. a lift shaft (see paragraph 5.34(b) that does not form a protected shaft in 2(b), (c) or (d) above.
E 30FD 30
5. Forming part of the enclosure of:
a. a protected lobby approach (or protected corridor) to a stairway or an evacuation shaft
E 30 Sa (2) FD 30 S(2)
b. any other protected corridor
E 20 Sa (2) FD 20 S(2)
c. a protected lobby approach to a lift shaft (paragraphs 5.37 to 5.39).
E 30 Sa (2) FD 30 S(2)
6. Giving access to an external escape route
E 30FD 30
7. Sub-dividing:
a. corridors connecting alternative exits
E 20 Sa (2) FD 20 S(2)
b. dead-end portions of corridors from the remainder of the corridor.
E 20 Sa (2) FD 20 S(2)
8. Any door within a cavity barrier
E 30FD 30
9. Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat
E 20FD 20
10. Any door that forms part of the enclosure:
a. to a place of special fire hazard
E 30FD 30
b. to ancillary accommodation in care homes (see paragraph 2.4).
E 30FD 30
11. In a dwellinghouse:
a. between a dwellinghouse and a garage
E 30 Sa (2) FD 30 S(2)
b. forming part of the enclosures to a protected stairway in a single family dwellinghouse
E 20FD 20
c. within any fire resisting construction in a dwellinghouse not described elsewhere in this table.
E 20FD 20

NOTES:

1. Classified in accordance with BS EN 13501-2. National classifications do not necessarily equate with European classifications, therefore products cannot typically assume a European class unless they have been tested accordingly.
2. Unless pressurisation techniques that comply with BS EN 12101-6 are used, these doors should also comply with one of the following conditions.
a. Have a leakage rate not exceeding 3m3/m/hour (from head and jambs only) when tested at 25Pa under BS 476-31.1.
b. Meet the additional Sa classification when tested to BS EN 1634-3.