Appendix C: Fire doorsets (2029 amendment) Table C1 Provisions for fire doorsets (2029 amendment)
Table C1 Provisions for fire doorsets (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table C1 Provisions for fire doorsets.
| Position of doorset | Minimum fire resistance of doorset in terms of integrity (minutes) when tested and classified to the relevant European standard(1) or assessed following the recommendations of paragraph B1 to B5 and C1(2) | |
|---|---|---|
| 1. | In a compartment wall separating buildings | Same as for the wall in which the door is fitted, but a minimum of 60 minutes |
| 2. | In a compartment wall: | |
a. if it separates a flat from a space in common use | 30 minutes Sa(3) | |
b. enclosing a protected shaft forming a stairway or an evacuation shaft wholly or partly above the adjoining ground in a building used for flats, other residential, assembly and recreation, or office purposes | 30 minutes Sa(3) | |
c. enclosing a protected shaft forming a stairway or an evacuation shaft not described in (b) above | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(3) | |
d. enclosing a protected shaft forming a lift or service shaft | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum | |
e. not described in (a), (b), (c) or (d) above. | Same as for the wall in which it is fitted, but add Sa(3) if the door is used for progressive horizontal evacuation under the guidance to requirement B1 | |
| 3. | In a compartment floor | Same as for the floor in which it is fitted |
| 4. | Forming part of the enclosures of: | |
a. a protected stairway or evacuation shaft (except as described in item 9 or 11(b) below) | 30 minutes Sa(3) | |
b. a lift shaft (see paragraph 5.34b) that does not form a protected shaft in 2(b), (c) or (d) above. | 30 minutes | |
| 5. | Forming part of the enclosure of: | |
a. a protected lobby approach (or protected corridor) to a stairway or an evacuation shaft. | 30 minutes Sa(3) | |
b. any other protected corridor | 20 minutes Sa(3) | |
c. a protected lobby approach to a lift shaft (paragraphs 5.37 to 5.39). | 30 minutes Sa(3) | |
| 6. | Giving access to an external escape route | 30 minutes |
| 7. | Sub-dividing: | |
a. corridors connecting alternative exits | 20 minutes Sa (3) | |
b. dead-end portions of corridors from the remainder of the corridor. | 20 minutes Sa(3) | |
| 8. | Any door within a cavity barrier | 30 minutes |
| 9. | Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat | 20 minutes |
| 10. | Any door that forms part of the enclosure: | |
a. to a place of special fire hazard | 30 minutes | |
b. to ancillary accommodation in care homes (see paragraph 2.44). | 30 minutes | |
| 11. | In a dwellinghouse: | |
a. between a dwellinghouse and a garage | 30 minutes Sa(3) | |
b. forming part of the enclosures to a protected stairway in a single family dwellinghouse | 20 minutes | |
c. within any fire resisting construction in a dwellinghouse not described elsewhere in this table. | 20 minutes | |
NOTES:
1. Classified in accordance with BS EN 13501-2. In the European classification ‘E’ is the resistance to fire in terms of integrity. Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.
2. When assessed as being capable of meeting a performance classification, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of integrity for a period of minutes, when following the recommendations of paragraphs B1 to B5.
3. Unless pressurisation techniques that comply with BS EN 12101-6 are used, these doors should also be evidenced to match in performance the additional Sa classification when tested to BS EN 1634-3.