Protected shafts Uninsulated glazed screens to protected shafts

Uninsulated glazed screens to protected shafts

8.34

An uninsulated glazed screen may be incorporated in the enclosure to a protected shaft between a stair and a lobby or corridor entered from the stair. The enclosure must conform to Diagram 8.4 and meet all of the following conditions.

a. The standard of fire resistance required for the protected stairway is not more than REI 60.
b. The glazed screen complies with the following.
i. It achieves a minimum rating of E 30.
ii. It complies with the guidance on limits on areas of uninsulated glazing in Appendix B, Table B3.
c. The lobby or corridor is enclosed with fire resisting construction achieving a minimum rating of REI 30.

8.35

Where the measures in Diagram 8.4 are not provided, then both of the following apply.

a. The enclosing walls should comply with Appendix B, Table B1.
b. The doors should comply with Appendix B, Table B3.

Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor. Wording on the drawing: paras 8.34 and 8.35; a. With corridor b. With lobby; External wall; Fire resistance of protected shaft to be a maximum of REI 60; Protected shaft; Protected; shaft; Corridor Uninsulated glazed screen (minimum RE 30) Uninsulated glazed screen (minimum RE 30); Fire resistance of construction to be a minimum of REI 30; Fire resistance of glazed screen to be a minimum of RE 30; Protected; lobby; Fire doorsets that are a minimum of E 30 Sa