Section 8: Compartmentation/sprinklers Protected shafts

Protected shafts

8.32

Any stair or other shaft passing directly from one compartment to another should be enclosed in a protected shaft. Protected shafts should be used for the following only, but may also include sanitary accommodation and washrooms.

a. Stairs.
b. Lifts.
c. Escalators.
d. Chutes.
e. Ducts.
f. Pipes.
g. Additional provisions apply for both of the following.
i. Protected shafts that are protected stairways: Sections 2 to 5.
ii. Stairs that are also firefighting stairs: Section 17.

Construction of protected shafts

8.33

The construction enclosing a protected shaft (Diagram 8.3) should do all of the following.

a. Form a complete barrier to fire between the compartments connected by the shaft.
b. Have the appropriate fire resistance given in Appendix B, Table B1, except for uninsulated glazed screens that meet the provisions of paragraph 8.34.
c. Satisfy the provisions for ventilation and the treatment of openings in paragraphs 8.38 and 8.39.

Diagram 8.3 Construction of protected shafts

Diagram 8.3 Construction of protected shafts. Wording on the drawing: See para 8.33; This diagram shows three common examples which illustrate the principles of the construction of protected shafts. The elements enclosing the shaft (unless formed by adjacent external walls) are compartment walls and floors.; Fd Fire doorset; Compartment wall; Fd Fd Fd Fd; External wall; A B C; Protected shaft A is bounded on three sides by compartment walls and on the fourth side by an external wall; Protected shaft C is a services duct bounded on four sides by compartment walls; Protected shaft B is bounded on four sides by compartment walls; The shaft structure (including any openings) should meet the relevant provisions for both of the following: compartment walls (see paragraphs 8.15 to 8.31) and external walls (see Sections 12 and 13 and Diagram 3.3).
Diagram 8.3 Construction of protected shafts

Uninsulated glazed screens to protected shafts

8.34

An uninsulated glazed screen may be incorporated in the enclosure to a protected shaft between a stair and a lobby or corridor entered from the stair. The enclosure must conform to Diagram 8.4 and meet all of the following conditions.

a. The standard of fire resistance required for the protected stairway is not more than REI 60.
b. The glazed screen complies with the following.
i. It achieves a minimum rating of E 30.
ii. It complies with the guidance on limits on areas of uninsulated glazing in Appendix B, Table B3.
c. The lobby or corridor is enclosed with fire resisting construction achieving a minimum rating of REI 30.

8.35

Where the measures in Diagram 8.4 are not provided, then both of the following apply.

a. The enclosing walls should comply with Appendix B, Table B1.
b. The doors should comply with Appendix B, Table B3.

Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor. Wording on the drawing: paras 8.34 and 8.35; a. With corridor b. With lobby; External wall; Fire resistance of protected shaft to be a maximum of REI 60; Protected shaft; Protected; shaft; Corridor Uninsulated glazed screen (minimum RE 30) Uninsulated glazed screen (minimum RE 30); Fire resistance of construction to be a minimum of REI 30; Fire resistance of glazed screen to be a minimum of RE 30; Protected; lobby; Fire doorsets that are a minimum of E 30 Sa
Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Pipes for oil or gas and ventilation ducts in protected shafts

8.36

A protected shaft containing a protected stairway and/or a lift should not also contain either of the following.

a. A pipe that conveys oil, other than in the mechanism of a hydraulic lift.
b. A ventilating duct. Two exceptions are as follows.
i. A duct provided for pressurising the protected stairway to keep it smoke free.
ii. A duct provided only to ventilate the protected stairway.

A pipe that is completely separated from a protected shaft by fire resisting construction is not considered to be contained within that shaft.

8.37

In a protected shaft, any pipe carrying natural gas or LPG should be both of the following.

a. Of screwed steel or all-welded steel construction.
b. Installed in accordance with both of the following.
i. The Pipelines Safety Regulations 1996.
ii. The Gas Safety (Installation and Use) Regulations 1998.

Ventilation of protected shafts conveying gas

8.38

A protected shaft conveying piped flammable gas should be ventilated direct to the outside air, by ventilation openings at high and low level in the shaft.

Any extension of the storey floor into the protected shaft should not compromise the free movement of air throughout the entire length of the shaft.

Guidance on shafts conveying piped flammable gas, including the size of ventilation openings, is given in BS 8313.

Openings into protected shafts

8.39

The external wall of a protected shaft does not normally need to have fire resistance. Situations where there are provisions are given in paragraph 3.29 (external walls of protected stairways, which may also be protected shafts) and paragraph 17.2 (firefighting shafts).

Openings in other parts of the enclosure to a protected shaft should be limited to the following.

a. If a wall common to two or more buildings forms part of the enclosure, only the following openings should be made in that wall.
i. A fire doorset providing a means of escape, which has the same fire resistance as the wall and is fitted in accordance with the provisions in Appendix C.
ii. The passage of a pipe that meets the provisions in Section 10.
b. Other parts of the enclosure (other than an external wall) should only have openings for any of the following.
i. Fire doorsets of the appropriate fire resistance, fitted in accordance with the provisions in Appendix C.
ii. The passage of pipes which meet the provisions in Section 10.
iii. Inlets to, outlets from and openings for a ventilation duct (if the shaft contains or serves as a ventilating duct), meeting the provisions in Section 10.
iv. The passage of lift cables into a lift machine room (if the shaft contains a lift). If the machine room is at the bottom of the shaft, the openings should be as small as practicable.