Design and protection of escape stairs Use of space within protected stairways

Use of space within protected stairways

3.38

A protected stairway may only include any of the following.

a. Sanitary accommodation or washrooms, as long as the accommodation is not used as a cloakroom. A gas water heater or sanitary towel incinerator may be installed in the accommodation, but no other gas appliance.
b. If the protected stairway is not a firefighting stair: a lift well.
c. If the protected stairway is not the only stair serving the building or part of the building: a reception desk or enquiry office area at ground or access level. The reception or enquiry office area should have a maximum area of 10m2.
d. If the protected stairway is not the only stair serving the building or part of the building: cupboards enclosed with fire resisting construction.