Width of escape stairs Worked examples
Worked examples
A 14 storey building contains 12 storeys of offices (ground + 11). The top two storeys contain flats that are served by separate stairs. What is the minimum width needed for the stairs that serve the office floors, for simultaneous evacuation? In the 11 above-ground-floor offices, 1200 people use the stairs. (People in the ground floor offices do not use the stairs.) In this example, two stairs are shown to satisfy the travel distance limitations.
a. The population is distributed evenly
The top office storey is at a height greater than 18m, therefore both stairs need lobby protection (see paragraph 3.34). Because both stairs are entered at each level via a protected lobby, both stairs can be assumed to be available (see paragraph 3.15).
P = 1200/2 = 600, N = 11
From the formula:
600 = 200W + 50 (W – 0.3)(11 – 1)
600 = 200W + (50W – 15)(10)
600 = 200W + 500W – 150
750 = 700W
W = 1070mm
Therefore both stairs should be at least 1070mm wide. But this needs to be increased to 1100mm, because the formula applies to stairs 1100mm wide or wider (see paragraph 3.18).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum widths needed for 110 people in Table 2.3).
b. The population is not distributed evenly
(e.g. 1000 people occupy floors 1 to 9, and 200 occupy floors 10 and 11).
The top office storey is at a height greater than 18m, therefore both stairs need lobby protection (see paragraph 3.34). Because both stairs are entered at each level via a protected lobby, both stairs can be assumed to be available (see paragraph 3.15).
To find the width of:
• the stairs serving floors 10 and 11:
P = 200/2 = 100, N = 2
From the formula:
100 = 200W + 50 (W – 0.3)(2 – 1)
100 = 200W + (50W – 15)(1)
100 = 200W + 50W – 15
115 = 250W
W = 460mm
Therefore both stairs between the 9th floor landing and the top floor should be at least 460mm wide. But this needs to be increased to 1100mm, because the formula applies to stairs 1100mm wide or wider (see paragraph 3.18).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum widths needed for 100 people in Table 2.3).
• the stairs serving floors 1 to 9:
P = 1200/2 = 600, N = 9
From the formula:
600 = 200W + 50 (W – 0.3)(9 – 1)
600 = 200W + (50W – 15)(8)
600 = 200W + 400W – 120
720 = 600W
W = 1200mm
Therefore both stairs between the ninth floor landing and the ground floor should be at least 1200mm wide.
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum widths needed for 134 people in Table 2.3).