Section 5: Walls Impervious cladding systems for walls

Impervious cladding systems for walls

5.19

Cladding systems for walls should:

a. resist the penetration of precipitation to the inside of the building; and
b. not be damaged by precipitation and not carry precipitation to any part of the building which would be damaged by it.

5.20

Cladding can be designed to protect a building from precipitation (often driven by the wind) either by holding it at the face of the building or by stopping it from penetrating beyond the back of the cladding.

5.21

Any cladding will meet the requirement if:

a. it is jointless or has sealed joints, and is impervious to moisture (so that moisture will not enter the cladding); or
b. it has overlapping dry joints, is impervious or weather resisting, and is backed by a material which will direct precipitation which enters the cladding towards the outer face.

5.22

Some materials can deteriorate rapidly without special care and they should only be used as the weather-resisting part of a cladding system if certain conditions are met (see Approved Document 7, Materials and workmanship). The weather-resisting part of a cladding system does not include paint nor does it include any coating, surfacing or rendering which will not itself provide all the weather resistance.

Technical solution

5.23

Cladding may be:

a. impervious including metal, plastic, glass and bituminous products; or
b. weather resisting including natural stone or slate, cement based products, fired clay and wood; or
c. moisture resisting including bituminous and plastic products lapped at the joints, if used as a sheet material, and permeable to water vapour unless there is a ventilated space directly behind the material; or
d. jointless materials and sealed joints, which would allow for structural and thermal movement.

5.24

Dry joints between cladding units should be designed so that precipitation will not pass through them, or the cladding should be designed so that precipitation which enters the joints will be directed towards the exposed face without it penetrating beyond the back of the cladding. Note: Whether dry joints are suitable will depend on the design of the joint or the design of the cladding and the severity of the exposure to wind and rain.

5.25

Each sheet, tile and section of cladding should be securely fixed. Guidance as to appropriate fixing methods is given in BS 8000-6:1990117. Particular care should be taken with detailing and workmanship at the junctions between cladding and window and door openings as they are vulnerable to moisture ingress.

5.26

Insulation can be incorporated into the construction provided it is either protected from moisture or unaffected by it.

5.27

Where cladding is supported by timber components or is on the façade of a timber framed building, the space between the cladding and the building should be ventilated to ensure rapid drying of any water that penetrates the cladding.

113 BRE Report BR 262 Thermal insulation: avoiding risks, 2002.

114 BRE Report 352 BRE Building elements: Walls, windows and doors, 2002.

115 BRE Report BR 292 Cracking in buildings, 1995.

116 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.

117 BS 8000-6:1990 Workmanship on building sites. Code of practice for slating and tiling of roofs and claddings.

Alternative approach

5.28

The requirement can also be met by following the relevant recommendations of:

a. BS CP 143118 for sheet roof and wall coverings made from the following materials:
Part 1:1958 Corrugated and troughed aluminium
Part 5:1964 Zinc
Part 10:1973 Galvanised corrugated steel
Part 12:1970 (1988) Copper
Part 15:1973 (1986) Aluminium
Part 16:1974 Semi-rigid asbestos bitumen sheets
Recommendations for lead are included in BS 6915:2001119;
b. BS 8219:2001120;
c. BS 8200:1985121;
d. BS 8297:2000122;
e. BS 8298:1994123;
f. MCRMA Technical Paper 6124;
g. MCRMA Technical Paper 9125.

These documents describe the materials and contain design considerations including recommendations for fixing.