Section 2: Resistance to contaminants Methane and other gases from the ground
Methane and other gases from the ground
Introduction
2.25
The term ‘methane and other gases’ is used to define hazardous soil gases which either originate from waste deposited in landfill sites or are generated naturally. It does not include radon which is dealt with separately in paragraphs 2.39 and 2.40. However, the term does include volatile organic compounds (VOCs). As stated in Limitations on Requirements above, measures described in this document are the minimum that are needed to comply with the Building Regulations. Further actions may be necessary to deal with the requirements of other legislation.
2.26
Landfill gas is generated by the action of micro-organisms on biodegradable waste materials in landfill sites. It generally consists of methane and carbon dioxide together with small quantities of VOCs which give the gas its characteristic odour. Methane and oxygen deficient atmospheres (sometimes referred to as stythe or black-damp) containing elevated levels of carbon dioxide and nitrogen can be generated naturally in coal mining areas. Methane and carbon dioxide can also be produced by organic rich soils and sediments such as peat and river silts. A wide range of VOCs can also be present as a result of petrol, oil and solvent spillages. Methane and other gases can migrate through the subsoil and through cracks and fissures into buildings.
2.27
Methane is an explosive and asphyxiating gas. Carbon dioxide although non-flammable is toxic. VOCs are not only flammable and toxic but can also have a strong, unpleasant odour. Should any of these gases build up to hazardous levels in buildings then they can cause harm to health or compromise safety.
Risk assessment
2.28
The risk assessment process outlined in paragraph 2.8 should also be adopted for methane and other gases. Further investigation for hazardous soil gases may be required where the ground to be covered by the building and/or any land associated with the building is:
2.29
There are documents that cover hazardous soil gases in these specific contexts:
8 Improving the flood performance of new buildings – Flood resilient construction, Communities and Local Government, Defra and the Environment Agency, May 2007.
58 Foundation for Water Research Report FR0448 Laying potable water pipelines in contaminated ground: guidance notes, 1994.
59 Assessment and management of risks to buildings, building materials and services from land contamination, Environment Agency, 2001.
60 HMIP Waste Management Paper No. 27 Landfill gas, 2nd edition, 1991.
61 Monitoring of landfill gas, Chartered Institution of Wastes Management (CIWM), 2nd edition, 1998.
2.30
During a site investigation for methane and other gases it is important to take measurements over a sufficiently long period of time in order to characterise gas emissions fully. This should also include periods when gas emissions are likely to be higher, e.g. during periods of falling atmospheric pressure. It is also important to establish not only the concentration of these gases in the ground but also the quantity of gas generating materials, their rate of gas generation, gas movement in the ground and gas emissions from the ground surface. This is an important part of the risk estimation stage. Indications about the gas regime in the ground can be obtained through surface emission rate and borehole flow rate measurements, and guidance on this is given in CIRIA Reports 15168 and 15269.
2.31
Construction activities undertaken as part of building development can alter the gas regime on the site. For example, a site strip can increase surface gas emissions as can piling and excavation for foundations, and dynamic compaction can push dry biodegradable waste into moist, gas-active zones.
2.32
When assessing gas risks in the context of traditional housing there is a need to consider two pathways for human receptors: (i) gas entering the dwelling through the sub-structure, and building up to hazardous levels, and (ii) subsequent householder exposure in garden areas which can include where outbuildings (e.g. garden sheds and greenhouses) and extensions are constructed, and where there may also be excavations for garden features (e.g. ponds).
2.33
Guidance on undertaking gas risk assessment is given in CIRIA Report 15269, and the GaSIM model is also available for assessing gas emissions from landfill sites70. There is further discussion of gas risk assessment in the Defra/ Environment Agency document CLR 1143.
2.34
CIRIA Report 14972 and the Department of the Environment, Transport and the Regions (DETR) Partners in Technology (PIT) report73 describe a range of ground gas regimes (defined in terms of soil gas concentrations of methane and carbon dioxide as well as borehole flow rate measurements) which can be helpful in assessing gas risks.
2.35
Depending on the proposed use, for non-domestic development the focus might be on the building only, but the general approach is the same.
Remedial measures
2.36
If the risks posed by the gas are unacceptable then these need to be managed through appropriate building remedial measures. Site-wide gas control measures may be required if the risks on any land associated with the building are deemed unacceptable. Such control measures include removal of the gas generating material or covering together with gas extraction systems. Further guidance is contained in CIRIA Report 14972. Generally speaking, expert advice should be sought in these circumstances.
2.37
Gas control measures for dwellings consist of a gas resistant barrier across the whole footprint (i.e. walls and floor) above an extraction (or ventilation) layer from which gases can be dispersed and vented to the atmosphere. They are normally passive, i.e. gas flow is driven by stack (temperature difference) and wind effects. Consideration should be given to the design and layout of buildings to maximise the driving forces of natural ventilation. Further guidance on this and detailed practical guidance on the construction of protective measures for housing is given in the BRE/Environment Agency report BR 41473. (In order to accommodate gas resistant membrane, for example as shown in BR414, the position and type of insulation may have to be adjusted). The DETR/Arup Environmental report74 compares the performance of a range of commonly used gas control measures and can be used as a guide to the design of such measures.
43 CLR 11. Model Procedures for the Management of Land Contamination. Defra/Environment Agency, 2004. www.environment-agency.gov.uk.
62 Institute of Petroleum TP 95 Guidelines for investigation and remediation of petroleum retail sites, 1998.
63 BGS Technical Report WP/95/1 Methane, carbon dioxide and oil seeps from natural sources and mining areas: characteristics, extent and relevance to planning and development in Great Britain, 1995.
64 Methane and other gases from disused coal mines: the planning response, DoE, 1996.
65 CIRIA Report 130 Methane: its occurrence and hazards in construction, 1993.
66 CIRIA Report 131 The measurement of methane and other gases from the ground, 1993.
67 CIRIA Report 150 Methane investigation strategies, 1995.
68 CIRIA Report 151 Interpreting measurements of gas in the ground, 1995.
69 CIRIA Report 152 Risk assessment for methane and other gases from the ground, 1995.
70 Environment Agency GasSIM – Landfill gas assessment tool.
72 CIRIA Report 149 Protecting development from methane, 1995.
2.38
Gas control measures for non-domestic buildings use the same principles as those used for housing, and the DETR/Arup Environmental report can also be used as a guide to design. Expert advice should be sought as the floor area of such buildings can be large and it is important to ensure that gas is adequately dispersed from beneath the floor. The use of mechanical (as opposed to passive) systems and monitoring and alarm systems may be necessary. There is a need for continued maintenance and calibration of these systems, so they are more appropriate with non-domestic buildings (as opposed to dwellings) since there is usually scope for this. Again, expert advice should be sought. Special sub-floor ventilation systems are carefully designed to ensure adequate performance and should not be modified unless subjected to a specialist review of the design. Such ventilation systems, particularly those using powered ventilation, are unlikely to be appropriate for owner occupied properties as there is a risk of interference by users.