Calculating exit capacity 2.23
2.23
If a ground floor storey exit and a stair share a final exit (via a ground floor lobby), then the final exit should be wide enough to evacuate people at a maximum flow rate equal to or greater than from the storey exit and stair combined (Diagram 2.6).
This can be calculated using the following formula:
W = ((N/2.5) + (60S))/80
where:
W is the width of final exit in metres
N is the number of people served by ground floor storey exit
S is the stair width in metres.
If the number of people (N) entering the lobby from the ground storey is more than 60, then the distance from the foot of the stair or the storey exit to the final exit should be a minimum of 2m (see Diagram 2.6).
If that minimum distance cannot be achieved, the width of the final exit (W) should be at least the width of the stair plus the width of the storey exit.