Escape route design Calculating exit capacity
Calculating exit capacity
2.21
Where multiple storey exits are available, fire might prevent one from being used. Remaining exits need to be wide enough for all occupants, so when using Table 2.3, the largest exit should be discounted.
Stairs should be at least as wide as any storey exit leading onto them. While some stairs are not subject to discounting (paragraphs 3.14 and 3.15), because the stairs will be available for other floors, the storey exits onto them are.
2.22
To calculate how many people two or more available exits (after discounting) can accommodate, add together the maximum numbers of people that each exit width can accommodate.
For example, three exits each 850mm wide accommodate 3×110 = 330 people.
2.23
If a ground floor storey exit and a stair share a final exit (via a ground floor lobby), then the final exit should be wide enough to evacuate people at a maximum flow rate equal to or greater than from the storey exit and stair combined (Diagram 2.6).
This can be calculated using the following formula:
W = ((N/2.5) + (60S))/80
where:
W is the width of final exit in metres
N is the number of people served by ground floor storey exit
S is the stair width in metres.
If the number of people (N) entering the lobby from the ground storey is more than 60, then the distance from the foot of the stair or the storey exit to the final exit should be a minimum of 2m (see Diagram 2.6).
If that minimum distance cannot be achieved, the width of the final exit (W) should be at least the width of the stair plus the width of the storey exit.
Diagram 2.6 Merging flows at final exit