Single escape routes and exits 2.6
2.6
A single escape route is acceptable for either of the following.
a. Parts of a floor from which a storey exit can be reached within the limit for travel distance in one direction shown in Table 2.1 (see also paragraph 2.8), provided the following apply.
i. For places of assembly and bars, no one room in this situation has more than 60 people.
ii. For ‘residential (institutional)’ buildings (purpose group 2(a)), no one room in this situation has more than 30 people. Occupant number calculations are described in Appendix D.
b. A storey with no more than 60 people, where the limits on travel distance in one direction only are satisfied (see Table 2.1).