Simultaneous evacuation 3.18

3.18

As an alternative to Table 3.2, the capacity of stairs 1100mm wide or wider can be found using either of the following formulas:

a. P = 200W + 50 (W – 0.3)(N – 1)
b. W = P + 15N – 15 / 150 + 50N

where:

P is the number of people that can be served

W is the width of the stair, in metres

N is the number of storeys served.

Separate calculations should be made for stairs serving basement storeys and stairs serving upper storeys.

The population, P, should be divided by the number of available stairs.

The formula is useful to determine the width of stairs where people are not distributed evenly – either within a storey or between storeys.

In the formula, 200W represents the number of people estimated to have left the stair after 2.5 minutes of evacuation, and 50 (W – 0.3)(N – 1) represents the number of people estimated to be on the stair after 2.5 minutes of evacuation.