Width of escape stairs Simultaneous evacuation

Simultaneous evacuation

3.16

The width of escape stairs should take account of the number of people using them while evacuating all storeys at the same time. The following stairs should be designed to allow simultaneous evacuation.

a. All stairs serving basements.
b. All stairs serving buildings with open spatial planning.
c. All stairs serving ‘residential (other)’ (purpose group 2(b)) or ‘assembly and recreation’ (purpose group 5) buildings.

Annexes B and C of BS 9999 include designs based on simultaneous evacuation.

3.17

The capacity of stairs of widths from 1000mm to 1800mm is given in Table 3.2.

Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building

No. of floors servedMaximum number of people served by a stair of width:
1000mm1100mm1200mm1300mm1400mm1500mm1600mm1700mm1800mm
1150220240260280300320340360
2190260285310335360385410435
3230300330360390420450480510
4270340375410445480515550585
5310380420460500540580620660
6350420465510555600645690735
7390460510560610660710760810
8430500555610665720775830885
9470540600660720780840900960
105105806457107758409059701035

NOTES:

1. The capacity of stairs that serve more than 10 storeys may be obtained by using linear extrapolation.
2. The capacity of stairs not less than 1100mm wide may also be obtained by using the formulas in paragraph 3.18.
3. Unless a central handrail is provided, stairs with a rise of more than 30m should be a maximum width of 1400mm (see paragraph 3.10).
4. Stairs wider than 2000mm should have a central handrail (see paragraph 3.11).

3.18

As an alternative to Table 3.2, the capacity of stairs 1100mm wide or wider can be found using either of the following formulas:

a. P = 200W + 50 (W – 0.3)(N – 1)
b. W = P + 15N – 15 / 150 + 50N

where:

P is the number of people that can be served

W is the width of the stair, in metres

N is the number of storeys served.

Separate calculations should be made for stairs serving basement storeys and stairs serving upper storeys.

The population, P, should be divided by the number of available stairs.

The formula is useful to determine the width of stairs where people are not distributed evenly – either within a storey or between storeys.

In the formula, 200W represents the number of people estimated to have left the stair after 2.5 minutes of evacuation, and 50 (W – 0.3)(N – 1) represents the number of people estimated to be on the stair after 2.5 minutes of evacuation.