Phased evacuation 3.21
3.21
A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.
a. At each storey except a top storey, stairs should be approached through a protected lobby or protected corridor.
b. At each storey, the lifts should be approached through a protected lobby (see paragraph 5.37).
c. Every floor should be a compartment floor (REI depending on height and use of the building).
d. If there is a storey over 30m above ground level, the building should be protected throughout by an automatic sprinkler system in accordance with Appendix E.
e. The building should be fitted with an appropriate fire warning system conforming to at least the L3 standard given in BS 5839-1.
f. An internal speech communication system should provide communication between a control point at fire and rescue service access level and a fire warden on every storey. The recommendations for phased evacuation provided in BS 5839-1 should be followed. Where it is deemed appropriate to install a voice alarm, this should be in accordance with BS 5839-8.