Width of escape stairs Phased evacuation
Phased evacuation
3.19
Phased evacuation cannot be used in every type of building, but can be advantageous for escape stairs in high buildings. It requires supporting facilities, such as fire detection and alarm systems, to be provided and maintained.
In a phased evacuation, the first people to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, subsequent evacuation is done two floors at a time, reducing disruption in large buildings.
Phased evacuation enables stairs to be narrower than with simultaneous evacuation, and may be used for any building provided it is not identified in paragraph 3.16.
3.20
Phased evacuation in buildings with a storey over 30m in height introduces the potential for escaping people to impede firefighters entering and operating within the building. This can be addressed by consulting with the fire and rescue service about special management procedures.
In very tall buildings, typically with a storey over 45m in height, physical measures may need to be incorporated, such as by discounting a stair.
3.21
A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.
3.22
The minimum width of stairs needed for phased evacuation is given in Table 3.3.
Table 3.3 Minimum width of stairs designed for phased evacuation
| Maximum number of people in any storey | Stair width (mm) |
|---|---|
| 100 | 1000 |
| 120 | 1100 |
| 130 | 1200 |
| 140 | 1300 |
| 150 | 1400 |
| 160 | 1500 |
| 170 | 1600 |
| 180 | 1700 |
| 190 | 1800 |
NOTES: