Width of escape stairs Phased evacuation

Phased evacuation

3.19

Phased evacuation cannot be used in every type of building, but can be advantageous for escape stairs in high buildings. It requires supporting facilities, such as fire detection and alarm systems, to be provided and maintained.

In a phased evacuation, the first people to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, subsequent evacuation is done two floors at a time, reducing disruption in large buildings.

Phased evacuation enables stairs to be narrower than with simultaneous evacuation, and may be used for any building provided it is not identified in paragraph 3.16.

3.20

Phased evacuation in buildings with a storey over 30m in height introduces the potential for escaping people to impede firefighters entering and operating within the building. This can be addressed by consulting with the fire and rescue service about special management procedures.

In very tall buildings, typically with a storey over 45m in height, physical measures may need to be incorporated, such as by discounting a stair.

3.21

A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.

a. At each storey except a top storey, stairs should be approached through a protected lobby or protected corridor.
b. At each storey, the lifts should be approached through a protected lobby (see paragraph 5.37).
c. Every floor should be a compartment floor (REI depending on height and use of the building).
d. If there is a storey over 30m above ground level, the building should be protected throughout by an automatic sprinkler system in accordance with Appendix E.
e. The building should be fitted with an appropriate fire warning system conforming to at least the L3 standard given in BS 5839-1.
f. An internal speech communication system should provide communication between a control point at fire and rescue service access level and a fire warden on every storey. The recommendations for phased evacuation provided in BS 5839-1 should be followed. Where it is deemed appropriate to install a voice alarm, this should be in accordance with BS 5839-8.

3.22

The minimum width of stairs needed for phased evacuation is given in Table 3.3.

Table 3.3 Minimum width of stairs designed for phased evacuation

Maximum number of people in any storeyStair width (mm)
1001000
1201100
1301200
1401300
1501400
1601500
1701600
1801700
1901800

NOTES:

1. This table assumes a phased evacuation of the fire floor first followed by evacuation of not more than two floors at a time.
2. Unless a central handrail is provided, stairs with a rise of more than 30m should be a maximum width of 1400mm (see paragraph 3.10).
3. As an alternative to using this table, the minimum width (in mm) may be calculated from: (P×10) – 100 where P = the number of people on the most heavily occupied storey. However, the minimum width of a stair should be 1000mm.