Non-residential buildings 8.11
8.11
In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.
a. Every wall needed to divide the building to observe the compartment size limits in Table 8.1 (Diagram 8.1a).
b. Every floor, if the building or separated part of the building (see paragraph 8.19) has a top storey that is more than 30m above ground level (Diagram 8.1b).
c. The floor of the ground storey, if the building has one or more basements (Diagram 8.1c), except in small premises (see paragraph 4.2).
d. The floor of every basement storey (except the lowest floor), if the building or separated part has a basement more than 10m below ground level (Diagram 8.1d).
e. If the building comprises ‘shop and commercial’, ‘industrial’ or ‘storage’ premises (purpose groups 4, 6, 7): every wall or floor dividing a building into separate occupancies (spaces used by different organisations, whether they fall within the same purpose group or not).
f. See also the provision in paragraph 5.46 for store rooms in shops to be separated from retail areas by fire resisting construction (minimum REI 30).