Provision of compartmentation Non-residential buildings
Non-residential buildings
8.11
In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.
a. Every wall needed to divide the building to observe the compartment size limits in Table 8.1 (Diagram 8.1a).
b. Every floor, if the building or separated part of the building (see paragraph 8.19) has a top storey that is more than 30m above ground level (Diagram 8.1b).
c. The floor of the ground storey, if the building has one or more basements (Diagram 8.1c), except in small premises (see paragraph 4.2).
d. The floor of every basement storey (except the lowest floor), if the building or separated part has a basement more than 10m below ground level (Diagram 8.1d).
e. If the building comprises ‘shop and commercial’, ‘industrial’ or ‘storage’ premises (purpose groups 4, 6, 7): every wall or floor dividing a building into separate occupancies (spaces used by different organisations, whether they fall within the same purpose group or not).
f. See also the provision in paragraph 5.46 for store rooms in shops to be separated from retail areas by fire resisting construction (minimum REI 30).
8.12
In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.
a. The area of the upper storey does not exceed the lower of:
i. 20% of the area of the ground storey
ii. 500m2.
b. The upper storey is compartmented from the lower one.
c. The upper storey has a means of escape independent of the lower storey escape routes.
Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.