Non-residential buildings 8.12
8.12
In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.
a. The area of the upper storey does not exceed the lower of:
i. 20% of the area of the ground storey
ii. 500m2.
b. The upper storey is compartmented from the lower one.
c. The upper storey has a means of escape independent of the lower storey escape routes.
Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.