Pipes for oil or gas and ventilation ducts in protected shafts 8.36

8.36

A protected shaft containing a protected stairway and/or a lift should not also contain either of the following.

a. A pipe that conveys oil, other than in the mechanism of a hydraulic lift.
b. A ventilating duct. Two exceptions are as follows.
i. A duct provided for pressurising the protected stairway to keep it smoke free.
ii. A duct provided only to ventilate the protected stairway.

A pipe that is completely separated from a protected shaft by fire resisting construction is not considered to be contained within that shaft.

View this page on RegsUK