Protected shafts Pipes for oil or gas and ventilation ducts in protected shafts
Pipes for oil or gas and ventilation ducts in protected shafts
8.36
A protected shaft containing a protected stairway and/or a lift should not also contain either of the following.
a. A pipe that conveys oil, other than in the mechanism of a hydraulic lift.
b. A ventilating duct. Two exceptions are as follows.
i. A duct provided for pressurising the protected stairway to keep it smoke free.
ii. A duct provided only to ventilate the protected stairway.
A pipe that is completely separated from a protected shaft by fire resisting construction is not considered to be contained within that shaft.
8.37
In a protected shaft, any pipe carrying natural gas or LPG should be both of the following.
a. Of screwed steel or all-welded steel construction.
b. Installed in accordance with both of the following.
i. The Pipelines Safety Regulations 1996.
ii. The Gas Safety (Installation and Use) Regulations 1998.