Openings in cavity barriers 9.17
9.17
Openings should be limited to the following.
a. Fire doorsets with a minimum rating of E 30, fitted in accordance with Appendix C.
b. The passage of pipes that follow the provisions in Section 10.
c. The passage of cables or conduits containing one or more cables.
d. Openings fitted with a suitably mounted and appropriate fire damper.
e. Ducts that are either of the following.
i. Fire resisting (minimum E 30).
ii. Fitted with a suitably mounted and appropriate fire damper where they pass through the cavity barrier.