Section 9: Cavities Construction and fixings for cavity barriers

Construction and fixings for cavity barriers

9.13

Cavity barriers, tested from each side separately, should provide a minimum of both of the following:

a. 30 minutes’ integrity (E 30)
b. 15 minutes’ insulation (I 15).

They may be formed by a construction provided for another purpose if it achieves the same performance.

9.14

Cavity barriers in a stud wall or partition, or provided around openings, may be formed of any of the following.

a. Steel, a minimum of 0.5mm thick.
b. Timber, a minimum of 38mm thick.
c. Polythene-sleeved mineral wool, or mineral wool slab, under compression when installed in the cavity.
d. Calcium silicate, cement-based or gypsum-based boards, a minimum of 12mm thick.

These do not necessarily achieve the performance specified in paragraph 9.13.

NOTE: Cavity barriers provided around openings may be formed by the window or door frame if the frame is constructed of steel or timber of the minimum thickness in (a) or (b), as appropriate.

9.15

Cavity barriers should be tightly fitted to a rigid construction and mechanically fixed in position. If this is not possible (e.g. where a cavity barrier joins to slates, tiles, corrugated sheeting or similar materials) the junction should be fire-stopped.

9.16

Cavity barriers should be fixed so their performance is unlikely to be made ineffective by any of the following.

a. Movement of the building due to subsidence, shrinkage or temperature change, and movement of the external envelope due to wind.
b. During a fire, collapse of services penetrating the cavity barriers, either by the failure of the supporting system or through degradation of the service itself (e.g. by melting or burning).
c. During a fire, failure of the cavity barrier fixings. (In roof spaces, where cavity barriers are fixed to roof members, there is no expectation of fire resistance from roof members provided for the purpose of support.)
d. During a fire, failure of any material or construction to which cavity barriers abut. (For example, a suspended ceiling that continues over a fire resisting wall or partition collapses, and the cavity barrier fails prematurely because the ceiling was not designed to provide a minimum fire resistance of EI 30.)

Openings in cavity barriers

9.17

Openings should be limited to the following.

a. Fire doorsets with a minimum rating of E 30, fitted in accordance with Appendix C.
b. The passage of pipes that follow the provisions in Section 10.
c. The passage of cables or conduits containing one or more cables.
d. Openings fitted with a suitably mounted and appropriate fire damper.
e. Ducts that are either of the following.
i. Fire resisting (minimum E 30).
ii. Fitted with a suitably mounted and appropriate fire damper where they pass through the cavity barrier.

9.18

If a cavity barrier is provided above or below a partition between bedrooms in ‘residential (institutional)’ and ‘residential (other)’ (purpose groups 2(a) and 2(b)) buildings, and the partition is not a fire resisting partition, then paragraph 9.17 does not apply. However, both of the following apply.

a. The number of openings in the barrier should be kept to a minimum.
b. Any penetrations should be sealed to restrict the passage of smoke with an appropriate fire-stopping material.

NOTE: For further guidance on openings in cavity barriers see Section 10.