Construction and fixings for cavity barriers Openings in cavity barriers

Openings in cavity barriers

9.17

Openings should be limited to the following.

a. Fire doorsets with a minimum rating of E 30, fitted in accordance with Appendix C.
b. The passage of pipes that follow the provisions in Section 10.
c. The passage of cables or conduits containing one or more cables.
d. Openings fitted with a suitably mounted and appropriate fire damper.
e. Ducts that are either of the following.
i. Fire resisting (minimum E 30).
ii. Fitted with a suitably mounted and appropriate fire damper where they pass through the cavity barrier.

9.18

If a cavity barrier is provided above or below a partition between bedrooms in ‘residential (institutional)’ and ‘residential (other)’ (purpose groups 2(a) and 2(b)) buildings, and the partition is not a fire resisting partition, then paragraph 9.17 does not apply. However, both of the following apply.

a. The number of openings in the barrier should be kept to a minimum.
b. Any penetrations should be sealed to restrict the passage of smoke with an appropriate fire-stopping material.

NOTE: For further guidance on openings in cavity barriers see Section 10.