Section 8: Compartmentation/sprinklers Construction of compartment walls and compartment floors
Construction of compartment walls and compartment floors
General provisions
8.15
All compartment walls and compartment floors should achieve both of the following.
8.16
Timber beams, joists, purlins and rafters may be built into or carried through a masonry or concrete compartment wall if the openings for them are both of the following.
If trussed rafters bridge the wall, failure of the truss due to a fire in one compartment should not cause failure of the truss in another compartment.
8.17
Where services could provide a source of ignition, the risk of fire developing and spreading into adjacent compartments should be controlled.
Compartment walls between buildings
8.18
Adjoining buildings should only be separated by walls, not floors. Compartment walls common to two or more buildings should comply with both of the following.
Separated parts of buildings
8.19
Compartment walls forming a separated part of a building should run the full height of the building in a continuous vertical plane.
Separated parts can be assessed independently to determine the appropriate standard of fire resistance in each. The two separated parts can have different standards of fire resistance.
Other compartment walls
8.20
Compartment walls not described in paragraphs 8.18 and 8.19 should run the full height of the storey in which they are situated.
8.21
Compartment walls in a top storey beneath a roof should be continued through the roof space.
Junction of compartment wall or compartment floor with other walls
8.22
At the junction with another compartment wall or an external wall, the fire resistance of the compartmentation should be maintained. Fire-stopping that meets the provisions in paragraphs 10.24 to 10.29 should be provided.
8.23
At the junction of a compartment floor and an external wall with no fire resistance, the external wall should be restrained at floor level. The restraint should reduce movement of the wall away from the floor if exposed to fire.
8.24
Compartment walls should be able to accommodate deflection of the floor, when exposed to fire, by either of the following means.
Where compartment walls are located within the middle half of a floor between vertical supports, the deflection may be assumed to be 40mm unless a smaller value can be justified by assessment. Outside this area, the limit can be reduced linearly to zero at the supports.
For steel beams that do not have the required fire resistance, reference should be made to SCI Publication P288.
Junction of compartment wall with roof
8.25
A compartment wall should achieve both of the following.
8.26
To reduce the risk of fire spreading over the roof from one compartment to another, a 1500mm wide zone of the roof, either side of the wall, should have a covering classified as BROOF(t4), on a substrate or deck of a material rated class A2-s3, d2 or better, as set out in Diagram 8.2a.
Thermoplastic rooflights that, because of paragraph 14.7, are regarded as having a BROOF(t4) classification are not suitable for use in that zone.
8.27
Materials achieving class B-s3, d2 or worse used as a substrate to the roof covering and any timber tiling battens, fully bedded in mortar or other suitable material for the width of the wall (Diagram 8.2b), may extend over the compartment wall in buildings that are both of the following.
8.28
Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.
8.29
As an alternative to the provisions of paragraph 8.26 or 8.27, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 8.2c).
Diagram 8.2 Junction of compartment wall with roof