Junction of compartment wall with roof Diagram 8.2 Junction of compartment wall with roof

Diagram 8.2 Junction of compartment wall with roof

Diagram 8.2 Junction of compartment wall with roof. Wording on the drawing: See paras 8.26 to 8.29; a. ANY BUILDING OR COMPARTMENT; Roof covering over this distance to be designated BROOF(t4) rated on deck of material of class A2-s3, d2 or better. Roof covering and deck could be composite structure, e.g. profiled steel cladding.; 1500mm 1500mm; Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.; If roof support members pass through the wall, fire protection to these members for a distance of 1500mm on either side of the wall may be needed to delay distortion at the junction (see paragraph 8.16).; Wall; Fire-stopping to be carried up to underside of roof covering, e.g. roof tiles.; b. RESIDENTIAL (OTHER), OFFICE, OR ASSEMBLY AND RECREATION USE, AND NOT MORE THAN 15M HIGH; Roof covering to be designated BROOF(t4) rated for at least this distance.; Boarding (used as a substrate) or timber tiling battens may be carried over the wall provided that they are fully bedded in mortar (or other no less suitable material) where over the wall.; X; Thermoplastic insulation materials should not be carried over the wall.; 1500mm 1500mm; Double-skinned insulated roof sheeting with a thermoplastic core should incorporate a band of material of class A2-s3, d2 at least 300mm wide centred over the wall.; Sarking felt may also be carried over the wall.; If roof support members pass through the wall, fire protection to these members for a distance of 1500mm on either side of the wall may be needed to delay distortion at the junction (see paragraph 8.16).; Wall; Fire-stopping to be carried up to underside of roof covering, boarding or slab.; X; Section X–X; Roof covering to be designated BROOF(t4) rated for at least 1500mm either side of wall.; Roofing battens and sarking felt may be carried over the wall.; Fire-stopping to be carried up to underside of roof covering above and below sarking felt.; NOTES: 1. Fire-stopping should be carried over the full thickness of the wall. 2. Fire-stopping should be extended into any eaves. 3. The compartment wall does not necessarily need to be constructed of masonry.; c. ANY BUILDING OR COMPARTMENT; At least 375mm; The wall should be extended up through the roof for a height of at least 375mm above the top surface of the adjoining roof covering.; At least 375mm; Roof covering; Where there is a height di˜erence of at least 375 mm between two roofs or where the roof coverings on either side of the wall are BROOF(t4) rated, the height of the upstand/parapet wall above the highest roof may be reduced to 200mm.; Roof covering; Wall
Diagram 8.2 Junction of compartment wall with roof

View this page on RegsUK